Plan Review Notes For Permit 15060302
Permit Number 15060302
Review Stop E
Sequence Number 1
Notes
Date Text
2015-06-22 10:43:446/22/2015
 PROJECT: LOFTIN PLACE FIRE ALARM
 PERMIT#: 14030096
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW REVISION TRACKING #15060302
 ACTION: DENIED
  
 REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW
 COMMENTS: SEE FIRE REVIEWER'S NOTES. ELECTRICAL REVIEW
 IS IN AGREEMENT.
  
 1) NO ADDRESS INDICATED ON THE PLANS OR IN THE
 TITLEBLOCK.
  
 2) NO REVISION CLOUDS, DELTAS OR DETAILED SUMMARY
 PROVIDED INDICATED WHAT HAS CHANGED ON THE PLANS.
  
 3) PLANS WERE ORIGINALLY SUBMITTED DIGITALLY; REVISION
 WAS SUBMITTED AS HARD COPY. PLEASE RESUBMIT THE REVISED
 PLANS DIGITALLY.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  