Plan Review Notes For Permit 15060299 |
Permit Number |
15060299 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-06-11 10:10:48 | APPROVED WITH EXCEPTION. THE PLANS HAVE BEEN APPROVED | | PROVISIONALLY. FAILURE TO CORRECT THE LISTED | | DEFICIENCIES PRIOR TO INSPECTION WILL RESULT IN FAILED | | INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION | | FEE(S). | | | | 1) ALL TRENCHES SHALL REMAIN OPEN FOR INSPECTION AND | | BURIAL DEPTHS SHALL COMPLY WITH NEC 300.5 | | | | 2) ALL MATERIALS TO BE LISTED FOR USE IN THE | | ENVIRONMENT IN WHICH THEY ARE INSTALLED. NEC 110.3 | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | 561-805-6717 OR [email protected] |
|