Plan Review Notes For Permit 15060259 |
Permit Number |
15060259 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-06-08 09:05:47 | 1)THE SCUPPER DIAGRAM IS CONFUSING. THE DIAGRAM SHOWS A | | NEW STORM DRAIN CONNECTION TO AN EXISTING VERTICAL RAIN | | WATER LEADER BUT THE SLOPE IS AWAY FROM THE CONNECTION | | TO THE LEADER . AS DRAWN IT WILL NOT DRAIN INTO THE | | LEADER. CLARIFY. | | 2) SCUPPERS SHALL DISCHARGE A MINIMUM OF 1 FOOT FROM | | THE STRUCTURE SIDEWALL PER 2010 FBC SEC.1503.7. | | 3)THE LETTER FROM THE ENGINEER NOTES THAT THERE ARE NO | | RATED ASSEMBLIES BEING REPAIRED, ALTERED OR REPLACED | | YET THE CONTRACTOR'S PROPOSAL REFERS TO FIRE COLLARS. | | CLARIFY. SUBMIT TWO COPIES OF DETAILS AND SPECS FOR THE | | FIRE COLLARS. THE ENGINEER SHALL REVIEW AND APPROVE THE | | TYPE OF FIRE COLLARS TO BE INSTALLED.WPB AMEND. TO 2010 | | FBC SEC.107.3.4.1. | | 4) THE OVERFLOW SCUPPERS SHALL BE INDEPENDENT OF THE | | PRIMARY SYSTEM PER FPC SEC. 1107.2. INDICATE SUCH ON | | THE PLANS. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | |
|