| PROJECT: EGRET REMODEL |
| PERMIT#: 15060250 |
| CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| ELECTRICAL PLAN REVIEW |
| ACTION: APPROVED WITH EXCEPTION. THE PLANS HAVE BEEN |
| APPROVED PROVISIONALLY. FAILURE TO CORRECT THE LISTED |
| DEFICIENCIES PRIOR TO INSPECTION WILL RESULT IN FAILED |
| INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION |
| FEE(S). |
| |
| 1) SMOKE DETECTORS ARE REQUIRED. WHEN ALTERATIONS, |
| REPAIRS, OR ADDITIONS REQUIRING A PERMIT OCCUR, OR WHEN |
| ONE OR MORE SLEEPING ROOMS ARE ADDED OR CREATED IN |
| EXISTING DWELLINGS, THE INDIVIDUAL DWELLING UNIT SHALL |
| BE EQUIPPED WITH SMOKE ALARMS LOCATED AS REQUIRED FOR |
| NEW DWELLINGS. FBC-RESIDENTIAL 314 AND 315. |
| |
| 2) ALL NEW GENERAL PURPOSE OUTLETS MUST BE TAMPER |
| RESISTANT AND AFCI PROTECTED. NEC 210.12, 406.11 |
| |
| 3) IN ADDITION TO THE NUMBER OF BRANCH CIRCUITS |
| REQUIRED BY OTHER PARTS OF THIS SECTION, AT LEAST ONE |
| 20-AMPERE BRANCH CIRCUIT SHALL BE PROVIDED TO SUPPLY |
| BATHROOM RECEPTACLE OUTLET(S). SUCH CIRCUITS SHALL HAVE |
| NO OTHER OUTLETS. NEC 210.52(C)(3) |
| |
| 4) ALL 125-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE |
| RECEPTACLES INSTALLED IN THE LOCATIONS SPECIFIED IN (1) |
| THROUGH (8) SHALL HAVE GROUND-FAULT CIRCUIT-INTERRUPTER |
| PROTECTION FOR PERSONNEL. (1) BATHROOMS NEC 210.8 |
| |