 PROJECT: EGRET REMODEL
 PERMIT#: 15060250
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 ELECTRICAL PLAN REVIEW
 ACTION: APPROVED WITH EXCEPTION. THE PLANS HAVE BEEN
 APPROVED PROVISIONALLY. FAILURE TO CORRECT THE LISTED
 DEFICIENCIES PRIOR TO INSPECTION WILL RESULT IN FAILED
 INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION
 FEE(S).
  
 1) SMOKE DETECTORS ARE REQUIRED. WHEN ALTERATIONS,
 REPAIRS, OR ADDITIONS REQUIRING A PERMIT OCCUR, OR WHEN
 ONE OR MORE SLEEPING ROOMS ARE ADDED OR CREATED IN
 EXISTING DWELLINGS, THE INDIVIDUAL DWELLING UNIT SHALL
 BE EQUIPPED WITH SMOKE ALARMS LOCATED AS REQUIRED FOR
 NEW DWELLINGS. FBC-RESIDENTIAL 314 AND 315.
  
 2) ALL NEW GENERAL PURPOSE OUTLETS MUST BE TAMPER
 RESISTANT AND AFCI PROTECTED. NEC 210.12, 406.11
  
 3) IN ADDITION TO THE NUMBER OF BRANCH CIRCUITS
 REQUIRED BY OTHER PARTS OF THIS SECTION, AT LEAST ONE
 20-AMPERE BRANCH CIRCUIT SHALL BE PROVIDED TO SUPPLY
 BATHROOM RECEPTACLE OUTLET(S). SUCH CIRCUITS SHALL HAVE
 NO OTHER OUTLETS. NEC 210.52(C)(3)
  
 4) ALL 125-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE
 RECEPTACLES INSTALLED IN THE LOCATIONS SPECIFIED IN (1)
 THROUGH (8) SHALL HAVE GROUND-FAULT CIRCUIT-INTERRUPTER
 PROTECTION FOR PERSONNEL. (1) BATHROOMS NEC 210.8
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  