2015-06-08 09:00:321ST REVIEW: FBC 2010 MECHANICAL
  
 1) SHOW THE SOURCE OF THE WATER SUPPLY FOR THE PROPOSED
 SPRINKLER SYSTEM: PLEASE NOTE THAT CONNECTION TO THE
 POTABLE WATER WILL REQUIRE INSTALLATION OF A RPZ
 BACKFLOW PREVENTER, AND A PLAN DETAIL SHOWING
 INSTALLATION LOCATION.
 2) PROVIDE AN ELECTRICAL PLAN.
  