Plan Review Notes
Plan Review Notes For Permit 15060235
Permit Number 15060235
Review Stop ENG
Sequence Number 1
Notes
Date Text
2015-06-15 09:32:43WATER SOURCE IS NOT SHOWN ON PLAN.
  
 WILL DOMESTIC WATER WILL BE USED FOR MAKE-UP WATER TO
 THE 300 GALLON TANK?
  
 CONFIRM 13D RESIDENTIAL FIRE SPRINKLER SYSTEM SYSTEM
 WILL BE SERVED FROM A POTABLE WATER SERVICE SOURCE.
  
 IF WATER METER IS SHUT DOWN DUE TO NON-PAYMENT OF THE
 MONTHLY SERVICE OR ANY OTHER MAINTENANCE ISSUE THEN A
 "FIRE WATCH" PER NFPA CODE WOULD BE REQUIRE AT THE
 OWNERS EXPENSE.
 OWNER SHALL HOLD HARMLESS AND INDEMNIFY THE CITY OF
 WEST PALM BEACH FROM ANY AND ALL LIABILITY ARISING FROM
 ANY SHUTDOWN."
  
 CODE REFERENCES
 NFPA 101 SECTION 9.6.1.8
 WHERE A REQUIRED FIRE ALARM SYSTEM IS OUT OF SERVICE
 FOR MORE THAN 4 HOURS IN A 24-HOUR PERIOD, THE
 AUTHORITY HAVING JURISDICTION SHALL BE NOTIFIED, AND
 THE BUILDING SHALL BE EVACUATED OR AN APPROVED FIRE
 WATCH SHALL BE PROVIDED FOR ALL PARTIES LEFT
 UNPROTECTED BY THE SHUTDOWN UNTIL THE FIRE ALARM SYSTEM
 HAS BEEN RETURNED TO SERVICE.
 NFPA 101 SECTION 9.7.6.1
 WHERE A REQUIRED AUTOMATIC SPRINKLER SYSTEM IS OUT OF
 SERVICE FOR MORE THAN 4 HOURS IN A 24-HOUR PERIOD, THE
 AUTHORITY HAVING JURISDICTION SHALL BE NOTIFIED, AND
 THE BUILDING SHALL BE EVACUATED OR AN APPROVED FIRE
 WATCH SHALL BE PROVIDED FOR ALL PARTIES LEFT
 UNPROTECTED BY THE SHUTDOWN UNTIL THE SPRINKLER SYSTEM
 HAS BEEN RETURNED TO SERVICE.
 A FIRE WATCH SHOULD AT LEAST INVOLVE SOME SPECIAL
 ACTION BEYOND NORMAL STAFFING, SUCH AS ASSIGNING AN
 ADDITIONAL SECURITY GUARD(S) TO WALK THE AREAS
 AFFECTED. THESE INDIVIDUALS SHOULD BE SPECIALLY TRAINED
 IN FIRE PREVENTION AND IN OCCUPANT AND FIRE DEPARTMENT
 NOTIFICATION TECHNIQUES, AND THEY SHOULD UNDERSTAND THE
 PARTICULAR FIRE SAFETY SITUATION FOR PUBLIC EDUCATION
 PURPOSES.
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 PUBLIC WORKS DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
  
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved