2015-06-18 16:44:41 | APPROVED WITH EXCEPTION. THE PLANS HAVE BEEN APPROVED | | PROVISIONALLY. FAILURE TO CORRECT THE LISTED | | DEFICIENCIES PRIOR TO INSPECTION WILL RESULT IN FAILED | | INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION | | FEE(S). | | | | 1) ALL NEW GENERAL PURPOSE OUTLETS MUST BE TAMPER | | RESISTANT AND AFCI PROTECTED. NEC 210.12, 406.11 | | | | 2) ALL 20-AMP RECEPTACLES INSTALLED IN THE KITCHEN | | SHALL HAVE GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION | | FOR PERSONNEL. NEC 210.8 (A) | | | | 3) RECEPTACLE OUTLETS SHALL BE INSTALLED SO THAT NO | | POINT ALONG THE WALL LINE IS MORE THAN 24" MEASURED | | HORIZONTALLY FROM A RECEPTACLE OUTLET IN THAT SPACE.NEC | | 210.52(C)(1) | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | 561-805-6717 OR [email protected] | | |
|