2015-07-28 11:34:23PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010 / 2008 NEC
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY ELECTRICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THERE IS NO WALL SWITCH SHOWN FOR THE SIX HIGH HATS
 IN THE KITCHEN. FBC 107.2.1
  
 2) THE 2/0 CU FEEDERS SHOWN IN THE RISER DIAGRAM ON E-1
 ARE REQUIRED TO HAVE A #4 GROUNDING ELECTRODE
 CONDUCTOR. NEC 250.68
  
 3) ON SHEET E-1, FOUR (4) #12 CU CONDUCTORS ARE
 SPECIFIED ON THE RISER DIAGRAM FOR THE GARDEN SHED. THE
 PANEL SCHEDULE SHOWS ONE 20 AMP CIRCUIT FOR THE GARDEN
 SHED, WHICH REQUIRES TWO (2) #12 CU CONDUCTORS. PLEASE
 CLARIFY. FBC 107.2.1
  
 4) ON THE MAIN HOUSE FLOOR PLAN THERE IS A SWITCHED
 DUPLEX OUTLET SHOWN ON THE LIVING ROOM CEILING. IS THIS
 A TYPO? PLEASE CLARIFY. FBC 107.2.1
  
 5) THE LOAD CALCULATIONS FOR THE HOUSE PANEL APPEARS TO
 HAVE AN ERROR. THE TOTAL CALCULATED LOAD IS 36.5. THE
 FIRST 10 KW AT 100 PERCENT MAKES THE BALANCE 26.5 KW.
 FORTY PERCENT OF 26.5 KW IS 10.6 KW NOT 7.4 KW. PLEASE
 CORRECT. FBC 107.2.1
  
 6) NEC 250.94 - INTERSYSTEM BONDING TERMINATION SHALL
 BE PROVIDED.
  
 7) NEC 250.104(B) THE GAS PIPING IS REQUIRED TO BE
 BONDED.
  
 8) NEC 410.16 (A) - (C) - LUMINAIRES IN CLOTHES CLOSETS
 SHALL BE OF THE TYPE PERMITTED AND LOCATED AS REQUIRED.
  
 9) CLARIFY WHAT IS LOCATED BESIDE THE REFRIGERATOR ON
 THE FAMILY ROOM SIDE. IF IT IS COUNTER SPACE A GFCI
 RECEPTACLE OUTLET IS REQUIRED. NEC 210.52 (3) (C)
  
 10) BOXES USED AT LUMINAIRE OR LAMP HOLDER OUTLETS IN A
 CEILING SHALL BE DESIGNED FOR THE PURPOSE AND SHALL BE
 REQUIRED TO SUPPORT A LUMINAIRE WEIGHING A MINIMUM OF
 23 KG (50 LB). BOXES USED AT LUMINAIRE OR LAMP HOLDER
 OUTLETS IN A WALL SHALL BE DESIGNED FOR THE PURPOSE AND
 SHALL BE MARKED TO INDICATE THE MAXIMUM WEIGHT OF THE
 LUMINAIRE THAT IS PERMITTED TO BE SUPPORTED BY THE BOX
 IN THE WALL, IF OTHER THAN 23 KG (50 LB). AT EVERY
 OUTLET USED EXCLUSIVELY FOR LIGHTING, THE BOX SHALL BE
 DESIGNED OR INSTALLED SO THAT A LUMINAIRE MAY BE
 ATTACHED. NEC 314.27(A)
  
 11) SMOKE ALARMS SHALL BE LOCATED PER MANUFACTURER'S
 INSTALLATION INSTRUCTIONS AND NFPA 72 SECTION 29.8.3.4.
 (4)*SMOKE ALARMS AND SMOKE DETECTORS SHALL NOT BE
 INSTALLED WITHIN AN AREA OF EXCLUSION DETERMINED BY A
 10 FT (3.0 M) RADIAL DISTANCE ALONG A HORIZONTAL FLOW
 PATH FROM A STATIONARY OR FIXED COOKING APPLIANCE,
 UNLESS LISTED FOR INSTALLATION IN CLOSE PROXIMITY TO
 COOKING APPLIANCES. SMOKE ALARMS AND SMOKE DETECTORS
 INSTALLED BETWEEN 10 FT (3.0 M) AND 20 FT (6.1 M) ALONG
 A HORIZONTAL FLOW PATH FROM A STATIONARY OR FIXED
 COOKING APPLIANCE SHALL BE EQUIPPED WITH AN
 ALARM-SILENCING MEANS OR USE PHOTOELECTRIC DETECTION.
 EXCEPTION: SMOKE ALARMS OR SMOKE DETECTORS THAT USE
 PHOTOELECTRIC DETECTION SHALL BE PERMITTED FOR
 INSTALLATION AT A RADIAL DISTANCE GREATER THAN 6 FT
 (1.8 M) FROM ANY STATIONARY OR FIXED COOKING APPLIANCE
 WHEN THE FOLLOWING CONDITIONS ARE MET:
 (A) THE KITCHEN OR COOKING AREA AND ADJACENT SPACES
 HAVE NO CLEAR INTERIOR PARTITIONS OR HEADERS AND
 (B) THE 10 FT (3.0 M) AREA OF EXCLUSION WOULD PROHIBIT
 THE PLACEMENT OF A SMOKE ALARM OR SMOKE DETECTOR
 REQUIRED BY OTHER SECTIONS OF THIS CODE.
 (5)*SMOKE ALARMS AND SMOKE DETECTORS SHALL NOT BE
 INSTALLED WITHIN A 36 IN. (910 MM) HORIZONTAL PATH FROM
 A DOOR TO A BATHROOM CONTAINING A SHOWER OR TUB.
  
  
  