2015-07-28 13:36:50 | PLAN |
| REVIEW COMMENTS |
| |
| 1ST REVIEW: FBC 2010 |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| DENIED BY BUILDING |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| 1) THE PLANS SPECIFY THAT THE EXISTING ASPHALT SHINGLE |
| ROOF ON THE MAIN HOUSE IS TO BE REPLACED WITH A |
| CONCRETE TILE ROOF. THE EXISTING ROOF IS REQUIRED TO BE |
| EVALUATED BY A FLORIDA LICENSED STRUCTURAL ENGINEER TO |
| DETERMINE THAT IT IS CAPABLE OF SAFELY SUPPORTING ALL |
| LOADS, INCLUDING DEAD LOADS, LIVE LOADS AND WINDS |
| LOADS. FBC - R301.1 |
| |
| 2) THE ROOF NOTES FOR THE PROPOSED DETACHED GARAGE ON |
| A-3 INCORRECTLY STATE REPLACE ASPHALT SHINGLES WITH |
| TILE. PLEASE CORRECT. FBC 107.2.1 |
| |
| 3) THE WORK THAT IS BEING DONE TO THE EXISTING BUILDING |
| INVOLVES RECONFIGURING SPACE AND THE WORK AREA EXCEEDS |
| 50 PERCENT OF THE BUILDING AREA. THIS CLASSIFIES IT AS |
| LEVEL 3 ALTERATION PER FBC EXISTING BUILDING CHAPTER 4. |
| THE DESIGN PROFESSIONAL IS REQUIRED TO NOTE THE LEVEL |
| OF ALTERATION ON THE PLANS PER SECTION 401.4. |
| |
| 4) THE VALUE OF THE ALTERATION WORK EXCEEDS 30 PERCENT |
| OF THE ASSESSED VALUE OF THE STRUCTURE AND IS |
| CONSIDERED A RENOVATED BUILDING BY THE 2010 FBC ENERGY |
| CONSERVATION. SUBMIT TWO SETS OF ENERGY CALCULATIONS |
| SHOWING THAT THE RENOVATED BUILDING COMPLIES WITH THE |
| ENERGY CODE. FBC ENERGY CONSERVATION 401.2 |
| |
| 5) THE PLANS SPECIFY A 4 PLY 2 X 12 WOOD BEAM AT THE |
| OPENING FROM THE DINING ROOM TO THE FAMILY ROOM THAT |
| WILL SUPPORT THE ALTERED ROOF TRUSSES. SPECIFY THE |
| FOOTING SIZES AND REINFORCEMENT THAT WILL BE REQUIRED |
| AT THE LOAD BEARING ENDS OF THIS BEAM. FBC-R301.1 |
| |
| 6) THE PRODUCT APPROVAL THAT WAS SUBMITTED HAS THE TWO |
| #8 SCREW MECHANICAL ATTACHMENT MARKED. THE PLANS |
| SPECIFY A FOAM-ON TILE APPLICATION AND A PRODUCT |
| APPROVAL FOR AH-160 FOAM ROOF TILE ADHESIVE WAS |
| SUBMITTED. PLEASE CLARIFY THE INSTALLATION THAT WILL BE |
| USED. |
| |
| 7) SHOW COMPLIANCE WITH TERMITE PROTECTION AT THE |
| PROPOSED GARAGE. FBC - R 318 |
| |
| 8) IN DETAIL B ON S-2 THE INTERIOR FOOTING REINFORCING |
| BARS ARE REQUIRED TO BE LAPPED AT THE CORNERS LIKE THE |
| OUTSIDE BARS IN ORDER TO BE CONTINUOUS. |
| |
| 9) ON SHEET S-2 THE GARAGE FOOTING IS SPECIFIED AS 20" |
| X 16" IN THE SCHEDULE AND AT SECTION C IT IS 16" X 16" |
| ,AS WELL AS, 1' 4" (16") X 1' 10" (22"). PLEASE CORRECT |
| SUCH THAT THE FOOTING SIZES ARE CONSISTENT. FBC 107.2.1 |
| |
| 10) SPECIFY THE MAXIMUM SPACING OF THE VERTICALLY |
| REINFORCED FILLED CELLS IN THE EXTERIOR WALLS OF THE |
| PROPOSED GARAGE. FBC - R 609.3.3 |
| |
| 11) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS |
| FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3 |
| THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD. PROVIDE TWO COMPLETE PRODUCT |
| APPROVALS WITH FL OR NOA NUMBERS INCLUDING INSTALLATION |
| INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES FOR EACH OF |
| THE SECTIONAL GARAGE DOOR. |
| |
| |
| |
| |
| |
| |