Plan Review Notes For Permit 15060144 |
Permit Number |
15060144 |
|
Review Stop |
B |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2015-10-27 08:45:50 | ***PROVISOS*** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | 1. SEPARATE PERMITS (APPLICATION, PLANS, AND FEES BASED | | ON VALUE) ARE REQUIRED FOR FENCES, SIGNS, MONUMENT | | SIGNS, PARKING LOT, SITE LIGHTING, ROOFTOP ALUMINUM | | CANOPY. | | | | 2. PRODUCT APPROVALS (AND FLOOR HATCH SPEC SHEETS) ARE | | TO BE SUBMITTED AND REVIEWED **PRIOR TO PRODUCT | | INSTALLATION**. ALL SUBMITTALS ARE TO BE REVIEWED BY | | DESIGNER OF RECORD PRIOR TO SUBMITTAL TO THE BUILDING | | DIVISION, FBC 107. | | PRODUCTS TO COMPLY WITH THE FOLLOWING DESIGN PRESSURES | | (SEE S7.5): | | | | ZONE 1: +16 / -57.8 | | ZONE 2 : +16 / -93 | | ZONE 3: +16 / -93 | | ZONE 4: +41.8 / -44 | | ZONE 5: +41.8 / -71 | | | | PROVIDE FIRE RESISTANCE RATING INFORMATION WITH PRODUCT | | APPROVALS, IF APPLICABLE. | | | | PROVIDE ROOF/FLOOR HATCH SPECS WITH FIRE RESISTANCE | | RATING INFORMATION | | | | 3. FBC 2010 603.1, PROVIDE INFORMATION REGARDING THE | | THE VINYL COVERED FENCE. THIS SECTION LISTS THE | | COMBUSTIBLES PERMITTED IN TYPE I AND II BUILDINGS. | | COMPLIANCE NOT CLEAR. THIS IS REQUIRED AS A SUBMITTAL | | PRIOR TO INSTALLATION. | | | | 4. THREE SETS OF ALL DOCUMENTS REQUIRED FOR ALL | | REVISIONS AND SUBMITTALS. | | | | 5. SPEC BOOK HAS NOT BEEN REVIEWED. A COPY MAY BE | | RETAINED AS A PART OF THE PERMIT FILE BUT IS NOT TO BE | | USED IN LIEU OF PLANS TO DEMONSTRATE CODE COMPLIANCE. | | | | |
|