Plan Review Notes
Plan Review Notes For Permit 15060144
Permit Number 15060144
Review Stop Z
Sequence Number 2
Notes
Date Text
2015-10-01 18:45:45FAILED
  
 PROVIDE RESPONSES IN WRITING.
  
 1) THIS PERMIT IS ONLY FOR THE GARAGE STRUCTURE. ALL
 OTHER ELEMENTS DEPICTED ON THE SITE PLANS HAVE NOT
 APPROVED BY ZONING. AS SUCH, THE FOLLOWING ITEMS
 REQUIRE SEPARATE PERMIT SUBMITTALS, WITH PLANS, AND
 HAVE NOT BEEN REVIEWED AS PART OF THIS PERMIT:
  
 A. LANDSCAPE, TO INCLUDE TREE REMOVAL AND RELOCATION.
 PLEASE NOTE CUS 1 THROUGH 3 ARE SHOWN IN LOCATIONS
 WHERE THE LANDSCAPE PLAN SHOWS HEDGES AND THE NEW FIRE
 HYDRANT ON THE NORTH SIDE OF THE BUILDING IS SHOWN
 WHERE TREES ARE SHOWN. NOTE: THE AS-BUILT PLANS WILL
 NEED TO BE SUBMITTED TO THE PLANNING DIVISION AS PART
 OF A MINOR PLANNED DEVELOPMENT AMENDMENT PRIOR TO THE
 C.O. FOR THE GARAGE.
 B. IRRIGATION
 C. PARKING GARAGE ACCESS LANES, TO INCLUDE PAVING,
 STRIPING, AND SIGNAGE
 D. BICYCLE RACKS
 E. EXTERIOR SIGNAGE
 F. WORK AND IMPROVEMENTS IN THE RIGHT-OF-WAY
 G. FENCES AND GATES NOT LOCATED WITHIN THE GARAGE
 H. GENERATOR AND ENCLOSURE
 I. HARDSCAPE, TO INCLUDE THE PAVERED ENTRY AREA AND
 SIDEWALKS
 J. SITE LIGHTING, TO INCLUDE PEDESTRIAN BOLLARDS -
 NOTE:
 1. THE PHILIPS LUMEC LEONIS SERIES OF LIGHTING DOES NOT
 COMPLY WITH THE DOWNTOWN STREET LIGHTING REQUIREMENTS.
 THE FIXTURE SHALL BE MOUNTED ON TOP OF THE POLE WITH
 THE LAMP CENTER AT 17 FEET ABOVE GRADE. THE PHILIPS
 LUMEC URBANSCAPE PRODUCT MOUNTED ON A POLE APPEARS THAT
 IT WOULD COMPLY WITH THE DOWNTOWN REQUIREMENTS.
 2. PLEASE REMEMBER THAT PALM BEACH COUNTY COMMITTED TO
 COORDINATING WITH RELATED TO USE THE SAME OR SIMILAR
 LIGHT FIXTURES IN THE FLORIDA AVENUE RIGHT-OF-WAY AND
 THE ENTRY DRIVE AND PLAZA TO MAINTAIN CONSISTENCY
 BETWEEN THE TWO PROJECTS. THE SPECIFIED TYPES DO NOT
 APPEAR TO BE CONSISTENT.
 3. THE POLES SHOWN IN THE CITY RIGHT-OF-WAY MAY NOT BE
 PERMITTED ON THE SITE LIGHTING PERMIT, BUT RATHER SHALL
 BE PERMITTED THROUGH THE ENGINEERING SERVICES DIVISION.
 4. ONE OF THE LIGHT POLES IS LOCATED WITHIN THE FIRE
 DEPARTMENT ACCESS DRIVEWAY.
 K. WORK WITHIN THE FUTURE STAGING AREA
  
 2) REPEAT COMMENT: SHEET AE160 HAS AN ARROW CALLING OUT
 THE ADA ACCESS AISLE AS YELLOW STRIPING. THIS STRIPING
 SHALL BE BLUE, NOT YELLOW.
  
 3) REPEAT COMMENT: SHEET AE501 AND SHEETS SW 120-SW170
 DO NOT SHOW COMPLIANCE WITH THE CONDITION THAT THE
 SIGNS WITHIN THE CONVENTION CENTER GARAGE GUIDE USERS
 TO THE ELEVATORS AND STAIRWELLS AT THE NORTHWEST CORNER
 OF THE CONVENTION CENTER GARAGE AND CLEARLY SIGN THE
 REMAINING STAIRWELLS AS EMERGENCY EGRESS ONLY. SIGN S23
 BEING SHOWN AT THE NORTHEAST STAIRWELL INDICATES THAT
 THE STAIRWELL IS FOR NORMAL EXITING OF THE GARAGE. IF
 THIS IS THE CASE, THEN THE EXIT TO THE STAIRWELL NEEDS
 TO BE CONNECTED INTO THE SITE SIDEWALK NETWORK ALONG
 THE NORTH SIDE OF THE GARAGE WITH NO LOSS OF LANDSCAPE.
 SIGN TYPE S22 IS SHOWN ON THE PLAN BUT NO DETAIL OF
 THIS SIGN IS INCLUDED.
  
 4) REPEAT COMMENT: THE PHOTOMETRICS ON EACH FLOOR NEED
 TO BE CONTINUED OUTSIDE OF THE GARAGE WALL TO THE
 PROPERTY LINE AROUND THE GARAGE.
  
 5) REPEAT COMMENT: PROVIDE INFORMATION ON HOW GLARE
 FROM THE INTERIOR AND EXTERIOR LIGHTS ONTO THE ADJACENT
 RESIDENTIAL PROPERTY AND RIGHTS-OF-WAY WILL BE
 CONTROLLED.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  