2015-09-30 10:14:16 | 2ND REVIEW: FBC 2010 MECHANICAL |
| PERMIT #15060144 |
| 9/30/15 |
| |
| 1) SHEET MM701: INDICATE THE DURATION OF OPERATION FOR |
| THE PRESSURIZATION FANS SF-1 & 2 AFTER DETECTION OF A |
| FIRE- REFER TO SECTION 909.4.6 FBC-10 BUILDING AND |
| PROVIDE NOTES TO CLARIFY. |
| 2) MM110: INDICATE HOW THE BASEMENT LEVEL UTILITY ROOMS |
| B005 & B006 ARE BEING VENTILATED. SHOW THE MEANS AND |
| PROVIDE CALCULATIONS- SECTION 401 FBC-10 MECHANICAL. |
| 3) MM220: PROVIDE VENTILATION CALCULATIONS FOR THE |
| UTILITY ROOM. PLEASE REFER TO SHEET AE140- THE UTILITY |
| ROOM IS ALSO FOUND ON FLOOR LEVELS 2,3,4,6, & 8; AND ON |
| FLOOR LEVELS 1,5, & 7 IT IS LABELED AS AN ELECTRICAL |
| ROOM . PLEASE SHOW THE MEANS OF VENTILATION FOR ALL OF |
| THESE ROOMS AND PROVIDE SIZING CALCULATIONS. |
| 4) MM220 & MM801: PROVIDE INSTALLATION AND SUPPORT |
| DETAILS FOR THE SF-1 AND SF-2 PRESSURIZATION FANS. |
| 5) MM801, DETAIL 11: THE HEIGHT OF THE RECIRCULATING |
| FANS ABOVE THE FINISH FLOORS SHALL BE MINIMUM 8' PER |
| SECTION 304.6 FBC-10 MECHANICAL. PLEASE CORRECT THE |
| DETAIL. |
| 6) MM802, DETAIL 3: THE DETAIL IS INCOMPLETE: PROVIDE |
| FASTENING DETAILS FOR ATTACHING THE CONDENSERS TO THE |
| BRACKET AND THE BRACKET TO THE WALL. DETAIL 4- PROVIDE |
| THE TYPE, SIZE, AND DEPTH OF EMBEDMENT FOR THE |
| CONDENSER TIE-DOWN ANCHOR BOLTS. PLEASE NOTE: SITE |
| SPECIFICA WINDLOAD ENGINEERING IS REQUIRED FOR ALL |
| EXTERIOR APPLIANCE INSTALLATIONS- SECTION 301.12 |
| /FBC-10 MECHANICAL. |
| 7) PROVIDE THE SEQUENCE OF OPERATION FOR THE |
| RECIRCULATION FANS, AND ALL OF THE VARIOUS ROOM EXHAUST |
| FANS. |
| 8) DUCTLESS SYSTEM 8 SHOWN IN THE SCHEDULE ON MM601 IS |
| NOT SHOWN ON THE PLANS- PLEASE INDICATE THE SYSTEM |
| LOCATION ON THE PLANS. |
| 9) AC CALCULATIONS WERE NOT PROVIDED FOR AC SYSTEMS 2, |
| 3, 6, 7, & 8- PLEASE PROVIDE THE CALCULATIONS. |
| 10) AC SYSTEMS 2, 3, 6, 7 & 8 ARE NOT LISTED IN THE |
| ENERGY CALCULATION FORM 506-2010- PLEASE PROVIDE THE |
| COMPLIANCE DATA. |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL PLANS EXAMINER |