Plan Review Notes
Plan Review Notes For Permit 15060144
Permit Number 15060144
Review Stop B
Sequence Number 2
Notes
Date Text
2015-10-10 15:20:37***PROVISO***
 ***ISSUED AT CONTRACTOR'S RISK***
 ***REVISION REQUIRED***
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. INFORMATIONAL ONLY; SEPARATE PERMITS REQUIRED FOR
 FENCES, SIGNS, MONUMENT SIGNS, PARKING LOT, SITE
 LIGHTING.
  
 2. INFORMATIONAL ONLY, PRODUCT APPROVALS ARE TO BE
 SUBMITTED AND REVIEWED PRIOR TO PRODUCT INSTALLATION.
 ALL SUBMITTALS ARE TO BE REVIEWED BY DESIGNER OF RECORD
 PRIOR TO SUBMITTAL TO THE BUILDING DIVISION, FBC 107.
  
 3. PROVIDE MORE INFORMATION REGARDING COST BREAKDOWN,
 FBC 109. IT IS NOT CLEAR HOW THE COST OF THE JOB
 DECREASED SIGNFICANTLY, ESPECIALLY IN LIGHT OF THE FACT
 THE CONSTRUCTION COSTS HAVE INCREASED SINCE
 APPLICATION. PROVIDE A COPY OF THE CONTRACT, FBC 109.
 PRIOR TO PAYMENT OF THIS PERMIT, FEES SHOULD BE
 RESOLVED AND APPLIED TO OTHER PERMITS AS APPLICABLE.
  
 4. AS000, REVISE SITE PLAN TO SHOW COMPLIANCE WITH FBC
 705.8, FBC 705.3 (ASSUMED PROPERTY LINE, DISTANCE OF
 EACH BUILDING TO THE ASSUMED PROPERTY LINE).
 INCORPORATE ANY EXCEPTIONS UTILIZED INTO THE PLAN.
 (THIS SHOULD BE CONSISTENT WITH THE CHANGES ALREADY
 MADE TO THE FOUNDATION PERMIT PLAN.)
  
 2ND REVIEW, THE PLAN SUBMITTED (AS000 DATED 9/4/15)
 DOES NOT INCLUDE FOUNDATION REVISION NUMBER 3 DATED
 6/9/15. THE PLAN SUBMITTED, ALTHOUGH THIS REVISION IS
 INCLUDED IN THE REVISION BLOCK, DOES NOT SHOW THE
 ASSUMED PROPERTY LINE CORRECTLY AND DOES NOT MATCH THE
 ISSUED FOUNDATION PERMIT. ALSO, THIS SHEET WAS REDLINED
 TO INCORPORATE EXCEPTIONS WHICH WERE INCLUDED IN THE
 RESPONSE LETTER BUT NOT INCLUDED ON THE PLAN.
  
 PROVIDE A PLAN CONSISTENT WITH THE ISSUED FOUNDATION
 PERMIT. IT IS UNCLEAR WHY THIS REVISION WOULD BE
 REMOVED FROM THIS SHEET. PLEASE CONFIRM THAT NO OTHER
 REVISIONS WERE REMOVED FROM THIS PLAN. A RE-REVIEW
 TYPICALLY TAKES LESS TIME AS ONLY NEW ITEMS ARE
 REVIEWED. IF REVISIONS WHICH WERE REQUIRED TO SHOW CODE
 COMPLIANCE ARE REMOVED FROM THE PLAN, A COMPLETE REVIEW
 OF THE ENTIRE PLAN IS REQUIRED AND TAKES SIGNIFICANTLY
 MORE TIME.
  
 4A. SEE FOUNDATION PERMIT, REVISION 15090442 SHEET
 AS000 AND ISSUED SHEET AS000. IT APPEARS THAT, ALTHOUGH
 THE DIMENSIONS DEMONSTRATING CODE COMPLIANCE FBC 705.8,
 705.3 WAS REMOVED, THAT CHANGE TO THE PLAN (REMOVAL OF
 REQUIRED DIMENSIONS) WAS NOT CLOUDED AND THEREFORE NOT
 REVIEWED. REVISE THIS SHEET AND SUBMIT AS A REVISION TO
 THE FOUNDATION PERMIT, INCORPORATING REDLINES WHICH
 INCLUDED THE EXCEPTIONS REFERRED TO IN THE RESPONSE
 LETTER (NOT A PART OF THE PERMIT RECORD). PLEASE SEE
 FOUNDATION COMMENT WHICH REQUESTED THAT ALL EXCEPTIONS
 UTILIZED BE INCORPORATED INTO THE PLAN (IN ORDER TO
 AVOID FIELD ISSUES AND TO CLEARLY DEMONSTRATE CODE
 COMPLIANCE).
  
 4B. TWO SHEETS WERE ENTIRELY NEW SHEETS SUBMITTED AS A
 REVISION TO THE FOUNDATION PERMIT (S8.2, S9.4) BUT WERE
 NOT INDICATED AS NEW SHEETS AND THEREFORE ONLY CLOUDED
 REVISIONS WERE REVIEWED. SUBMIT A NEW INDEX AS A
 REVISION TO THE FOUNDATION PERMIT INDICATING THE NEW
 SHEETS. CONFIRM THAT ALL CHANGES IN THAT REVISION WERE
 CLOUDED. IN ADDITION TO THE CHANGE ON AS000, SEE
 F-PP110D; THIS SHEET INCLUDES A CHANGE WHICH WAS NOT
 CLOUDED. OTHER CHANGES WERE MADE TO THE STRUCTURAL
 SHEETS WHICH WERE NOT CLOUDED. PLEASE CONFIRM THAT ALL
 REVISIONS TO THE ISSUED FOUNDATION PERMIT WERE PROPERLY
 CLOUDED AND, IF ANY CHANGES WERE NOT, PLEASE CLOUD AT
 THIS TIME AND SUBMIT WITH THE REVISION SO THOSE ITEMS
 CAN BE REVIEWED. DISCREPANCIES WERE FOUND ON TWO S
 SHEETS, BUT A THOROUGH REVIEW WAS NOT DONE, ONLY A SPOT
 CHECK.
  
 SHEET AS000 TO BE CORRECTED AND SUBMITTED AS A
 REVISION.
  
 5. PROVISO, FBC 1008, PER ARCHITECT, BOTH MEANS OF
 EGRESS GATES WILL INCLUDE PANIC HARDWARE.
  
 6. PROVISO, FBC 2010 ACCESSIBILITY 502.5, HEIGHT
 RESTRICTION SIGNAGE REQUIRED FOR ACCESSIBLE VANS.
  
 7. PROVISO, PROVIDE CALCULATIONS AND MORE INFORMATION
 TO DOCUMENT THE PERCENTAGES (OPEN PARKING GARAGE) SHOWN
 ON AE201 AND AE202. CALCULATIONS AND REPORT PREPARED BY
 SARAH MAMAN PE, FIRE PROTECTION ENGINEER, HAS BEEN
 RECEIVED VIA EMAIL; SIGNED, SEALED, DATED ORIGINALS
 REQUIRED. SUBMIT AS A "SUBMITTAL" (NO FEE).
  
 8. PROVISO, PROVIDE ARCHITECT'S EXHIBIT "C" (ADDITIONAL
 DOCUMENTATION FOR "OPEN" CLASSIFICATION) FULL SIZE
 SHEETS, SIGNED AND SEALED (SUBMITTAL, NO FEE).
  
 9. PROVISO, FBC 2010 ACCESSIBILITY 209.4, 503, REVISE
 PLAN TO SHOW THE VEHICULAR PULL UP SPACE AND ACCESS
 AISLE. SUBMIT AS A REVISION. (RESPONSE LETTER STATES
 THAT THIS IS SHOWN ON AE172 AND REVISED CIVIL DRAWINGS.
 SEE SECTION 503.3.3, THE ACCESS AISLE IS TO BE MARKED.
 IT IS NOT CLEAR ON AE172 WHERE THE LOADING ZONE IS
 LOCATED AND I WAS UNABLE TO FIND THE MARKED ACCESS
 AISLE, PLEASE REVISE PLAN. PLEASE REVISE PLANS TO SHOW
 DIMENSIONS OF FBC 2010 ACCESSIBILITY 503.2, THE PULL UP
 SPACE, AND 503.3, THE MARKED ACCESS AISLE. AN
 ACCESSIBLE PASSENGER LOADING ZONE COMPLIANT WITH 503 IS
 REQUIRED. RESPONSE APPEARS TO INDICATE AGREEMENT FROM
 THE DESIGNER, BUT IT IS NOT CLEAR HOW THIS HAS BEEN
 ADDRESSED.)
  
 10. PROVISO, FBC 2010 603.1, PROVIDE INFORMATION
 REGARDING THE THE VINYL COVERED FENCE. THIS SECTION
 LISTS THE COMBUSTIBLES PERMITTED IN TYPE I AND II
 BUILDINGS. COMPLIANCE NOT CLEAR. THIS IS REQUIRED AS A
 SUBMITTAL PRIOR TO INSTALLATION.
  
 ***REQUIRED PRIOR TO PERMIT ISSUANCE***
  
 11. SEE SHEETS SA1 THROUGH 6D AND OTHER SHEETS AS
 APPLICABLE, AS000, THE THRESHOLD STATEMENTS ARE NOT
 CONSISTENT WITH FLORIDA STATUTE 553.79(7)(D). PLEASE
 REVISE OR CLARIFY.
  
 THE LANGUAGE IN FS 553.79:
  
 ALL PLANS FOR THE BUILDING WHICH ARE REQUIRED TO BE
 SIGNED AND SEALED BY THE ARCHITECT OR ENGINEER OF
 RECORD CONTAIN A STATEMENT THAT, TO THE BEST OF THE
 ARCHITECT?S OR ENGINEER?S KNOWLEDGE, THE PLANS AND
 SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM
 BUILDING CODES AND THE APPLICABLE FIRESAFETY STANDARDS
 AS DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH
 THIS CHAPTER AND CHAPTER 633.
  
 STATEMENT ON STRUCTURAL SHEETS:
  
 TO THE BEST OF THE ENGINEER'S KNOWLEDGE, THE PLANS AND
 SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM
 BUILDING CODES AND THE LOCAL AUTHORITY IN ACCORDANCE
 WITH THIS SECTION AND 633 FLORIDA STATUTES.
  
 (NOTE THAT LANGUAGE NOT CONSISTENT WITH STATUTE.)
  
 STATEMENT ON AS000:
  
 TO THE BEST OF ARCHITECT?S KNOWLEDGE, THE PLANS AND
 SPECIFICATIONS COMPLY WITH THE APPLICABLE FIRE SAFETY
 STANDARDS AS DETERMINED BY THE LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND 633 FLORIDA STATUTE.
  
 (NOTE THAT MINIMUM BUILDING CODES WAS OMITTED.)
  
 PLEASE EITHER REVISE THE STATEMENT TO BE CONSISTENT
 WITH THE STATUTE OR EMAIL RATIONALE FOR LANGUAGE WHICH
 DEVIATES FROM THE STATUTE.
  
  
  