2015-07-08 14:16:121)THERE ARE SEVERAL SHEETS IN THE FRONT OF THE PLANS
 THAT NOTE FOR REFERENCE ONLY-SEE E 15040015. WHAT IS
 THIS IN REFERENCE TO? CLARIFY.
 2)SHT. AE160 DETAILS #2 & #3 SHOWS A ROOF DRAIN &
 PIPING/OVERFLOW DRAIN LOCATED IN THE STAIRWELLS AND
 PENETRATING THE WALL OF THE ENCLOSURE. PENETRATIONS
 INTO AND OPENINGS THROUGH AN EXIT ENCLOSURE ARE
 PROHIBITED IN ACCORDANCE WITH THE 2010 FBC SEC.1022.4.
 3)SHT.AE 179 - SHOW THE DEPTH OF THE GUTTER ON DETAILS
 #2 & #5. WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 4)SHT. AE 401 - SHOW THE INSIDE CLEAR DIMENSIONS (L X
 W) OF THE ACCESSIBLE RESTROOM.
 5)SHT.AE 401 - SHOW THE CLEAR FLOOR SPACE FOR THE BREAK
 ROOM SINK PER FAC SEC. 606. THE CLEAR FLOOR SPACE SHALL
 BE CENTERED ON THE FIXTURE.
 6)SHT. AE 404 - SHOWS PERFORATED DRAIN PIPE AT
 PERIMETER OF OUTER WALL OF STRUCTURE. SUBMIT DETAILS:
 SIZE OF PIPE, DEPTH AND WIDTH OF BALLAST ROCK, AND SHOW
 LOCATION ON PLANS. I COULD NOT LOCATE THIS PIPING ON
 THE CIVIL DRAWINGS. WPB AMEND. TO 2010 FBC SEC.
 107.2.1.
 7) CALCULATIONS FOR THE SIZING OF RAIN WATER DRAINAGE
 FOR THE ROOF OF THE STAIRWELLS SHALL INCLUDE - THE AREA
 OF ANY VERTICAL WALL THAT DIVERTS RAINWATER TO THE ROOF
 SHALL BE INCLUDED IN THE CALCULATIONS. 2010 FPC SEC.
 1106.4.
 8) INDICATE ON THE PLANS IF THE ELEVATOR IS HYDRAULIC
 OR TRACTION. IF HYDRAULIC, THE CYLINDER SHALL COMPLY
 WITH THE 2010 FBC SEC.3011.1 THRU 3011.1.3.
 9) SUBMIT A DETAIL DRAWING FOR THE BOOSTER PUMP FOR THE
 POTABLE WATER SYSTEM. WPB AMEND. TO 2010 FBC SEC.
 107.2.1.
 10) SHT.PP110A - SHOWS A 2"INDIRECT WASTE LINE THAT
 APPEARS TO BE PENETRATING THE WALL OF STAIR #1.
 PENETRATIONS INTO AND THROUGH AN EXIT ENCLOSURE ARE
 PROHIBITED EXCEPT FOR THE ITEMS LISTED IN 2010 FBC
 1022.4. CLARIFY.
 11) SUBMIT SIZING CALCULATIONS FOR THE OIL INTERCEPTOR.
 THE PLANS SHOW A SCHIER OIL INTERCEPTOR. THE SIZING
 CALCULATIONS SHALL BE REVIEWED BY SCHIER FOR CORRECT
 SIZING PER THE 2010 FPC SEC. 1003.2. PLEASE CONTACT LEE
 SCHNEEWEISS, SCHIER REPRESENTATIVE AT 1-800-538-4792.
 12) SHT.PP110B - INDICATE THE SLOPE OF THE 10 INCH & 12
 INCH STORM DRAIN LINES ON GRID LINE #F BETWEEN GRID
 LINE 10-1. NOTE: THE SQUARE FOOTAGE DRAINED SHALL
 COMPLY WITH 2010 FPC TABLE 1106.3.
 13) SHT.PP160D - SHOW THE CONTINUATION POINT OF THE 6_
 RAIN WATER DRAIN (SEE GRID LINES 2-3 & C-D). IS THIS
 TURNING UP OR DOWN? AND TO WHERE?
 14) SHT.PP 170A - THE PLAN SHOWS A 4" STORM DRAIN
 DISCHARGING ABOVE THE TOP LEVEL NEXT TO A PARKING
 SPACE. THIS APPEARS THAT IT MAY CAUSE A NUISANCE DUE TO
 THE DISCHARGING WATER FOR THAT PARKING AREA DURING A
 RAIN EVENT. THE SAME ISSUE OCCURS BY STAIR #2. CLARIFY.
 15) SHT. PP 170A - THERE IS A HORIZONTAL SECTION OF 4"
 STORM THAT IS COLLECTING 2170 SQUARE FEET OF AREA. THE
 MAXIMUM SQUARE FOOTAGE THAT A 4" HORIZONTAL STORM DRAIN
 CAN ACCOMMODATE AT AN 1/8" PER FOOT SLOPE AND A 5"
 RAINFALL RATE IS 1504 SQUARE FEET PER TABLE 1106.3.
 ADJUST THE SIZE TO THE NEXT LARGER PIPE SIZE OR
 INCREASE THE SLOPE.
 16) SHT.PP170C - SHOWS A 6" O.D. SERVING 4500 SQ. FT.
 THE MAXIMUM SQUARE FOOTAGE AT 1/8? PER FT. SLOPE IS
 4280 SQ. FT. PER TABLE 1106.3.
 17) SHT. PP180A & PP180B - SHOW THE SQUARE FOOTAGE
 DRAINED BY EACH DRAIN. ALSO SHOW THIS ON THE STORM
 WATER RISER. COMPLY WITH TABLE 1106.3 OF THE 2010 FPC.
 18) SHT. PP401 - SUBMIT A WATER ISOMETRIC FOR THE PUMP
 ROOM AND SUBMIT AN ELEVATION/PIPING DETAIL FOR THE
 DOMESTIC BOOSTER PUMP. WPB AMEND. TO 2010 FBC SEC.
 107.3.5.1.3.
 19) SHT. PP501 -SHOW THE SQUARE FOOTAGE OF THE AREA
 BEING DRAINED BY EACH DRAIN FOR THE STORM WATER RISERS.
 ALL VERTICAL LEADERS SHALL BE SIZED IN ACCORDANCE WITH
 THE 2010 FPC TABLE 1106.2 (1), 1106.2 (2) & ALL
 HORIZONTAL PIPING SHALL BE SIZED IN ACCORDANCE WITH
 TABLE 1106.3.ALL SIZING SHALL BE BASED ON A RAINFALL
 RATE OF 5 INCHES PER HOUR.
 20) INDICATE THE SLOPE OF THE HORIZONTAL STORM DRAIN
 PIPING. COMPLY WITH TABLE 1106.3 OF 2010 FPC.
 21) SHT.PP502 - THE AUTOMATIC AIR VENT CONNECTION TO
 THE HORIZONTAL DRAIN SHALL COMPLY WITH 2010 FPC SEC.
 905.3. THE VENT SHALL CONNECT TO THE HORIZONTAL DRAIN
 ABOVE THE CENTERLINE OF THE HORIZONTAL DRAIN PIPE.
 CHECK ALL OF THE AAV CONNECTIONS. SEE ALSO 4? LINE AT
 HUB DRAIN BY STAIR #2.
 22) SHT. PP502 - SUBMIT AN ENLARGED SANITARY RISER FOR
 THE GROUND LEVEL RESTROOM, BREAKROOM AND JANITOR. THE
 RISER IS TOO SMALL TO REVIEW.
 23) SHT. PP503 -A SHUT-OFF VALVE IS REQUIRED AT THE
 BASE OF THE WATER RISER PER 2010 FPC SEC. 606.1 (4).
 24) SHT. PP504 - SHOW THE SQUARE FOOTAGE DRAINED BY
 EACH 4? ROOF DRAIN. COMPLY WITH 2010 FPC TABLE 1106.3.
  
  