2015-06-24 14:57:211ST REVIEW: FBC 2010 MECHANICAL
  
 1) PROVIDE AN EXHAUST VENTILATION CALCULATION FOR THE
 BASEMENT LEVEL PARKING GARAGE TO VERIFY EF-1, 2, & 3
 HAVE BEEN SIZED TO PROVIDE THE RATES REQUIRED BY TABLE
 403.3 AND SECTION 404 FBC-10 MECHANICAL.
 2) CLARIFY THE METHOD BY WHICH THE STAIR PRESSURIZATION
 FANS (EF-4, 5 AND SF-1,2) WERE SIZED: PROVIDE
 CALCULATIONS CONSISTENT WITH SECTION 909.6 INCLUSIVE
 FBC-10 BUILDING.
 3) PROVIDE EXHAUST VENTILATION CALCULATIONS FOR THE
 BOOSTER PUMP, STORAGE, AND FIRE PUMP ROOMS- ASHRAE
 62.1-07.
 4) PROVIDE AC LOAD CALCULATIONS FOR ALL CONDITIONED
 ROOMS AND SPACES IN ACCORDANCE WITH ACCA MANUAL N, OR
 ASHRAE/ACCA STANDARD 183- REFERENCE SECTION 503.2.1
 FBC-10 ENERGY CONSERVATION.
 5) PROVIDE ENERGY CALCULATIONS FOR THE PROPOSED PROJECT
 PER SECTION101 FBC-10 ENERGY: SUBMIT TWO COPIES OF
 EITHER FORM 502 OR 506 SIGNED BY THE DESIGN
 PROFESSIONAL OF RECORD.
 6) SHEET MM110: PROVIDE ADDITIONAL DETAILS OR NOTES
 INDICATING THE SPACING AND MOUNTING HEIGHT LOCATIONS OF
 THE C0 DETECTORS PER THE MANUFACTURER'S
 RECOMMENDATIONS. LIST THE MAKE AND MODEL NUMBERS OF THE
 DEVICES AND SUBMIT PRODUCT DATA SHEETS REVIEWED AND
 APPROVED BY THE DESIGN PROFESSIONAL OF RECORD.
 7) MM220: CU 3 & 6 SHOWN IN DETAIL 8 SHALL BE INSTALLED
 A MINIMUM OF 8 FT. ABOVE THE FLOOR PER SECTION 304.6
 FBC-10 MECH.
 8) MM230: THE BOTTOM OF THE EXHAUST LOUVERS FOR THE
 BASEMENT EXHAUST FANS AS SHOWN IN DETAIL 4 SHALL BE
 INSTALLED A MINIMUM OF 10 FT. ABOVE THE ADJOINING
 GRADE- SECTION 501.2.1(2) FBC-10 MECH.
 9) MM801: THE RECIRCULATING FANS SHOWN IN DETAIL 11
 SHALL BE INSTALLED AT LEAST 1FT. HIGHER THAN THE GARAGE
 DOOR PER SECTION 304.6.
 10) MM801: PROVIDE INSTALLATION DETAILS FOR THE
 FIRE/SMOKE DAMPERS, AND THE DUCT SMOKE DETECTORS.
 11) PROVIDE A SUBMITTAL PACKAGE PREPARED BY THE DESIGN
 PROFESSIONAL OF RECORD THAT INCLUDES: A) FLORIDA
 PRODUCT APPROVALS AND/OR MIAMI-DADE NOA'S FOR THE ROOF
 MOUNTED EXHAUST FANS, THE INTAKE AND EXHAUST LOUVERS,
 AND THE CONDENSER WALL MOUNT BRACKETS. B)
 MANUFACTURER'S SPECIFICATIONS FOR THE EXHAUST AND
 INTAKE FANS, THE AC UNITS, THE MOTORIZED INTAKE
 DAMPERS, THE C0 DETECTORS, THE RECIRCULATION FANS, THE
 FIRE/SMOKE DAMPERS, AND THE DUCT SMOKE DETECTORS. IN
 REGARD TO ALL EXTERIOR INSTALLATIONS SUBJECT TO WIND
 LOAD, THE DESIGN PROFESSIONAL OF RECORD SHALL CALCULATE
 DESIGN PRESSURES AND PROVIDE TIE-DOWN ENGINEERING, AND
 ALSO CIRCLE OR HIGHLIGHT ALL APPLICABLE NOTES AND
 DETAILS IN THE NOA'S AND PRODUCT APPROVALS.
 12) PLEASE NOTE THAT THE ABOVE REVIEW COMMENTS ARE
 BASED ON THE BUILDING BEING CLASSIFIED AS AN "OPEN
 PARKING GARAGE" BY THE DESIGN PROFESSIONAL OF RECORD.
 THIS CLASSIFICATION IS BEING CHALLENGED BY THE WEST
 PALM BEACH FIRE AND RESCUE DEPT., THEREFORE ADDITIONAL
 COMMENTS MAY FOLLOW THIS REVIEW.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719