Plan Review Notes
Plan Review Notes For Permit 15060144
Permit Number 15060144
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2015-06-08 16:19:39THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) SHEET LS 110, THE PROPOSED PROJECT SHALL MEET THE
 REQUIREMENTS OF THE 5TH EDITION OF FLORIDA FIRE
 PREVENTION CODE INCLUDING THE 2012 EDITION OF NFPA 1
 AND NFPA 101 AND ALL OTHER APPLICABLE CODES OR
 STANDARDS. PLEASE MAKE CORRECTIONS TO THE DRAWING SET.
  
 2) SHEET LS110 EXIT #126 SE, LEADS TO AN AREA THAT HAS
 LOCKED GATES AND IS NOT LEADING TO A PUBLIC WAY. THE
 EXIT IS NONCONFORMING
  
 3) SHEET LS 120 EXITS # 105 S MIDDLE & 133.SE, LEAD TO
 AN AREA THAT HAS LOCKED GATES AND IS NOT LEADING TO A
 PUBLIC WAY. THESE EXITS ARE NONCONFORMING
  
 4) EXIT SIGNAGE DIRECTIONAL'S ON ALL FLOOR LEVELS SHALL
 BE REVIEWED AND ADJUSTED TO POINT IN THE DIRECTION OF
 THE EXIT.
  
 5) THE GATES ATEACH END OF THE FIRE LANE NOTE A KNOX
 BOX LOCATION. THE KNOX BOX CAN ONLY BE ACCESSED FROM
 ONE DIRECTON. GATE ACCESS SHALL BE FROM BOTH
 DIRECTIONS.
  
 6) THERE IS INSUFFICIENT INFORMATION PROVIDED TO
 DETERMINE THAT IT IS AN OPEN PARKING STRUCTURE. THE
 DEFINITION AND CONSTRUCTION OF THIS AS AN OPEN PARKING
 STRUCTURE IS NOT APPROVED. THE METAL FACADE STRUCTURE
 DOES NOT PROVIDE EACH PARKING LEVEL OPENINGS TO THE
 ATMOSPHERE. ADDITIONALLY, THE OPENINGS ARE NOT
 DISTRIBUTED OVER 40 PERCENT OF THE BUILDING PERIMETER
 OR UNIFORMLY OVER TWO OPPOSING SIDES. OPEN PARKING
 STRUCTURES PROVIDE FOR VENTILATION. WITH THE ADDITION
 OF THE METAL FACADE THE VENTILATION IS SIGNIFICANTLY
 REDUCED THAN IF THE THE AREAS WERE FULLY OPEN
  
 THE METAL FACADE IS A PERFORMANCE BASED OPTION OF AN
 OPEN PARKING STRUCTURE. PLEASE PROVIDE ADDITIONAL
 INFORMATION AS OUTLINED IN NFPA 1, CHAPTER 5
 PERFORMANCE BASED OPTION FOR REVIEW AND CONSIDERATION
 OF AN OPEN PARKING STRUCTURE.
  
 THERE APPEARS TO BE NO WAY TO MEASURE OR TEST THAT THE
 PROPOSED WILL PROVIDE FOR VENTILATION.
  
 7) BASED ON # 6, THE PARKING STRUCTURE IS REQUIRED TO
 BE FULLY SPRINKLED WITH MECHANICAL VENTILATION.
  
 8) SHEET AE301, PROVIDE ADDITIONAL MORE DETAILED
 INFORMATION FOR THE STATEMENT, " VEHICLE RESTRAINT
 CABLE SYSTEM TYP. WITH WOVEN EXTERIOR ACRYLIC FABIC
 SCREEN WITH REINFORCED VINYL EDGES ONLY @ PERIMETER OF
 THE BUILDING."
 WHAT PURPOSE DOES IT SERVE? IS THIS FABRIC LFMAE
 RETARDENT? IS THIS FABRIC COVERING CALCULATED IN THE
 OPEN GARAGE FORMULA? THIS AREA WOULD NOT BE OPEN TO THE
 ATMOSPHERE AND SHOULD BE CLACULATED AS CLOSED.
  
 9) THE FIRE HYDRANT AND FDC ARE IN LOCATIONS THAT ARE
 NOT READILY ACCESSIBLE TO FIRE APPARATUS. THE HYDRANT
 AND FDC SHOULD BE MOVED OUT IN THE AREA OF THE FIRE
 COMMAND CENTER AND KNOX BOX.
  
 10) THERE APPEARS TO BE ONLY ONE WATER SUPPLY TO THE
 STRUCTURE, TWO ARE REQUIRED.
  
 11) SHEET FA 701, RISER LEGEND # 10, REMOTE GENERATOR
 STATUS PANEL SHALL INCLUDE AN ADDITIONAL STATEMENT OF
 "MANUAL START AND TRANSFER FEATURES"