Plan Review Notes For Permit 15060144 |
Permit Number |
15060144 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-08-31 19:52:26 | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS | | EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE | | MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO | | THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE | | CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW. | | | | 1. THE EXIT LIGHT DEFICIENCY IS TYPICAL THROUGH OUT THE | | LEVELS. THERE SHALL BE AN EXIT LIGHT MID WAY IN EACH OF | | THE PARKING AISLES. | | 2. THE DIRECTION OF THE FACE OF THE LIGHTS SHALL BE | | REVIEWED AS WELL. | | 3. THE PANEL LABELS DO NOT MATCH THOSE INDICATED ON THE | | RISER DIAGRAM. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE | | PREVIOUSLY REVIEWED SHEETS. | | | | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO | | CONTACT ME DIRECTLY. | | |
|