2015-07-16 18:20:34 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL |
| BUILDING PLANS EXAMINER |
| [email protected] |
| 561-805-6724 |
| |
| 1. INFORMATIONAL ONLY; SEPARATE PERMITS REQUIRED FOR |
| FENCES, SIGNS, MONUMENT SIGNS, PARKING LOT, SITE |
| LIGHTING. |
| |
| 2. PROVIDE A COST BREAKDOWN FOR THE PROJECT. SOME ITEMS |
| WILL REQUIRE SEPARATE PERMITS (SUCH AS THE PARKING LOT |
| AND LANDSCAPING) AND SHOULD NOT BE INCLUDED IN THE |
| BUILDING PERMIT VALUE. |
| |
| 3. INFORMATIONAL ONLY, PRODUCT APPROVALS ARE TO BE |
| SUBMITTED AND REVIEWED PRIOR TO PRODUCT INSTALLATION. |
| ALL SUBMITTALS ARE TO BE REVIEWED BY DESIGNER OF RECORD |
| PRIOR TO SUBMITTAL TO THE BUILDING DIVISION, FBC 107. |
| |
| 4. AS000, REVISE SITE PLAN TO SHOW COMPLIANCE WITH FBC |
| 705.8, FBC 705.3 (ASSUMED PROPERTY LINE, DISTANCE OF |
| EACH BUILDING TO THE ASSUMED PROPERTY LINE). |
| INCORPORATE ANY EXCEPTIONS UTILIZED INTO THE PLAN. |
| (THIS SHOULD BE CONSISTENT WITH THE CHANGES ALREADY |
| MADE TO THE FOUNDATION PERMIT PLAN.) |
| |
| 5. LS110 AND C2.00, FBC 1008.2, PROVIDE A DETAIL FOR |
| THE GATES AND GATE HARDWARE FOR THE PEDESTRIAN GATES |
| ADJACENT TO THE FIRE LANE. THE GATES ARE TO MEET ALL OF |
| THE REQUIREMENTS AS DOORS AS THEY ARE IN THE EXIT |
| DISCHARGE FOR SEVERAL EXITS. |
| |
| 6. C3.05, LEGEND DOES NOT INCLUDE THE GRAPHIC FOR THE |
| FIRE LANE. ON OTHER SHEETS, THE FIRE LANE IS NOTED AS |
| STABILIZED GRADE. LS110, THE SIDEWALK WHICH LEADS TO |
| THE TWO GATES APPEAR TO BE BLOCKED BY STAIRS (FOR |
| EXAMPLE, SEE STAIR 3 AND DOOR 105). IN OTHER AREAS (SE |
| STAIR TO BASEMENT, SE CORNER OF BUILDING) SIDEWALK |
| WIDTH IS NOT CLEAR. SEE FBC 1003.1, 1005.1, 1003.4, |
| 1003.5. ARE OCCUPANTS TO WALK AROUND THE STAIRS, ON THE |
| FIRE LANE, WHICH APPEARS UNPAVED? |
| |
| 7. LS110 AND C2.00, THE EXIT AT THE SOUTH (AND OTHER |
| EXITS) APPEAR TO BE OBSTRUCTED BY OTHER STAIRS |
| (SIDEWALK NOT CONTINUOUS). SEE FBC 1003.6, MEANS OF |
| EGRESS CONTINUITY. REVISE THE LIFE SAFETY PLAN TO SHOW |
| EXIT DISCHARGE, ROUTE TO THE PUBLIC WAY, WITH MORE |
| INFORMATION REGARDING THE FIRE EXIT LANE (SHOWN AS |
| "STABLILIZED" RATHER THAN PAVED) AS IT APPEARS THAT |
| OCCUPANTS WILL BE FORCED TO WALK ACROSS THE FIRE LANE, |
| AROUND THE STAIRS, AS A PART OF THE EXIT DISCHARGE. |
| |
| 8. LS120, FBC 2010 ACCESSIBILITY 208.3, 103, AND TITLE |
| II ADA (STATE AND LOCAL GOVERNMENT REQUIREMENTS), THERE |
| ARE SEVERAL ELECTRICAL VEHICLE SPACES BUT IT DOES NOT |
| APPEAR THAT ANY OF THEM ARE USABLE BY AN INDIVIDUAL WHO |
| REQUIRES AN ACCESSIBLE SPACE. AT LEAST ONE OF THE |
| SPACES IS REQUIRED TO BE ACCESSIBLE (MEETING THE |
| PARKING SPACE DIMENSION REQUIREMENTS, ACCESS AISLE). IT |
| IS RECOMMENDED THAT AN EMAIL ADVISING HOW THIS WILL BE |
| ADDRESSED IS SUBMITTED PRIOR TO PLAN RESUBMITTAL FOR A |
| COURTESY REVIEW TO AVOID REPEAT COMMENTS. |
| |
| 9. LS SHEETS, SEE FBC 1007, FBC 2010 ACCESSIBILITY 207, |
| PLEASE IDENTIFY METHOD OF COMPLAINCE AND NOTE |
| ACCESSIBLE EXITS ON THE PLAN. A REVIEW OF THIS ITEM HAS |
| NOT BEEN DONE AS METHOD SELECTED (IBC 2001 OR IBC 2003) |
| HAS NOT BEEN DETERMINED. PLEASE NOTE THAT, SINCE THE |
| BUILDING IS NOT SPRINKLERED AT THIS TIME, IT APPEARS |
| THAT AREA OF REFUGE WILL BE REQUIRED. |
| |
| TO AVOID POSSIBLE COMMENTS ON THIS ITEM, A COURTESY |
| REVIEW CAN BE REQUESTED PRIOR TO RESUBMITTAL. |
| |
| 10. LS120, FBC 2010 ACCESSIBILITY 502.5, HEIGHT |
| RESTRICTION SIGNAGE REQUIRED FOR ACCESSIBLE VANS. |
| |
| 11. LS110, ALLOWABLE AREA IS SHOWN USING FBC TABLE |
| 406.3.5 FOR OPEN PARKING GARAGES. SEE FIRE COMMENTS. IF |
| THIS BUILDING IS DETERMINED TO BE AN ENCLOSED PARKING |
| GARAGE, PLEASE CONTACT ME TO DISCUSS HOW TO PROCEED. |
| |
| 12. PROVIDE CALCULATIONS AND MORE INFORMATION TO |
| DOCUMENT THE PERCENTAGES (OPEN PARKING GARAGE) SHOWN ON |
| AE201 AND AE202, ESPECIALLY THE GROUND LEVEL (SHOWN AS |
| 20.5%; 20% REQUIRED). AS THIS ISSUE IS CRUCIAL TO THE |
| ENTIRE REVIEW AND BUILDING DESIGN, THIS INFORMATION CAN |
| BE SENT VIA EMAIL FOR PRELIMINARY REVIEW PRIOR TO |
| RESUBMITTAL OF THE PLAN. |
| |
| THIS REVIEW IS BEING PERFORMED TREATING THE BUILDING AS |
| AN OPEN PARKING GARAGE. PLEASE NOTE THAT, SUBJECT TO |
| REVIEW OF CALCULATIONS FOR THE OPENINGS REQUIRED, IF |
| ADDITIONAL ITEMS ARE ADDED WHICH EXCEED CODE COMPLIANCE |
| FOR AN OPEN PARKING GARAGE, THE ADDITIONAL SYSTEMS WILL |
| NOT AFFECT THE DESIGNATION OF OPEN PARKING GARAGE. THE |
| CLASSIFICATION OF OPEN PARKING GARAGE WILL BE BASED ON |
| OPENING CALCULATIONS AND THE DEFINITION IN THE FBC. |
| |
| **7/17/15 - CALCULATIONS AND REPORT PREPARED BY SARAH |
| MAMAN PE, FIRE PROTECTION ENGINEER, HAS BEEN RECEIVED |
| VIA EMAIL (PENDING REVIEW AND MEETING)** |
| |
| 13. FBC 2010 ACCESSIBILITY 209.4, 503, REVISE PLAN TO |
| SHOW THE VEHICULAR PULL UP SPACE AND ACCESS AISLE. |
| |
| 14. LS110, 0 FIRE RATING SHOWN FOR THE ROOF; FBC TABLE |
| 601 REQUIRES 1 HOUR, FOOTNOTE B APPLIES IF THE ROOF IS |
| OVER 20FT ABOVE THE FLOOR BELOW. PLEASE REVISE OR |
| INCORPORATE APPLICABLE EXCEPTION INTO THE PLAN FOR 0 HR |
| FIRE RATING. |
| |
| 15. LS110, BUILDING HEIGHT AND AREA ADDRESSES ONLY THE |
| S2 OCCUPANCY. PLEASE REVISE TO INCLUDE THE BUSINESS |
| OCCUPANCY. IS THIS AREA BEING TREATED AS AN ACCESSORY |
| OR MIXED USE? SEE FBC 508. NO FIRE RATED SEPARATIONS |
| SHOWN BETWEEN BUSINESS AND S2. |
| |
| 16. LS110 AND OTHER SHEETS, FBC 708.14.1, ELEVATOR |
| LOBBY WALL IS NOT SHOWN AS A FIRE PARTITION. EITHER |
| REVISE PLAN TO INCLUDE REQUIRED FIRE RATING OR |
| INCORPORATE AN APPLICABLE EXCEPTION INTO THE PLAN. |
| |
| 17. LS110, FBC 509.3(5) STATES THAT THE GROUP S2 |
| ENCLOSED PARKING GARAGE IS FOR THE EXCLUSIVE USE OF |
| PARKING, BUT ALLOWS AN OFFICE, WAITING ROOM AND TOILET |
| ROOM NOT TO EXCEED 1000 SF, AND MECHANICAL EQUIPMENT |
| ROOMS IN THE ENCLOSED PARKING GARAGE PORTION. THIS |
| SHEET SHOWS THREE UTILITY SPACES, B004, B005 AND B006 |
| AND ONE UNIDENTIFIED SPACE (ADJACENT TO B004). IT DOES |
| NOT APPEAR THAT THE CODE ALLOWS THE UTILITY SPACES, AND |
| MORE INFORMATION IS REQUIRED FOR THE UNIDENTIFIED |
| SPACE. PROVIDE SF AREA AND RATIONALE FOR THESE SPACES |
| OR REVISE TO BE CONSISTENT WITH THE ALLOWABLE USES IN |
| THE CODE. |
| |
| 18. LS110, PLEASE CORRECT THE TYPO FBC 1022.1 EXCEPTION |
| 4 (PLAN STATES EXCEPTION 5 WHICH IS NOT APPLICABLE). |
| |
| 19. LS110, PLEASE CORRECT THE APPARENT TYPO (OR |
| CLARIFY) FBC 905.3.1, EXCEPTION 3 REFERS TO AREAS |
| SUBJECT TO FREEZING. |
| |
| 20. LS120, PROVIDE DIMENSIONS FOR THE FIRE COMMAND |
| CENTER, FBC 403.4.5, 911.1.3. |
| |
| 21. LS120, STAIRS 1 AND 2, WILL THERE BE SIGNAGE TO |
| HELP TO PREVENT OCCUPANTS FROM ATTEMPTING TO ENTER THE |
| BASEMENT DOOR RATHER THAN THE EXIT? NOT REQUIRED BUT |
| RECOMMENDED. |
| |
| 22. LS130 AND OTHER SHEETS, CLARIFY USE OF THE UTILITY |
| SPACE AND INCLUDE THESE SPACES ON LS110 (SQUARE FOOT |
| AREAS, OCCUPANCY CLASSIFICATION, HOW THEY ARE |
| CLASSIFIED FBC 508). |
| |
| 23. FBC 1009.6.2, IT APPEARS THAT THE SOME OF THE EXIT |
| STAIRS WILL BE EXPOSED TO THE WEATHER. PROVIDE |
| INFORMATION (CROSS SLOPE?) TO SHOW HOW WATER WILL BE |
| PREVENTED FROM ACCUMULATING. |
| |
| 24. AE160, SPECIFY DESIGN PRESSURES FOR THE PROPOSED |
| ROOF HATCHES. IT APPEARS THAT THEY WILL BE IN ZONE 2. |
| |
| 25. AE152, DETAILS 1 AND 5, IDENTIFY THE SQUARES WHICH |
| APPEAR TO BE HATCHES. |
| |
| 26. ENERGY CALCS REQUIRED, FBC 2010 ENERGY CONSERVATION |
| 103. |
| |
| 27. FBC 2010 ENERGY CONSERVATION, CONFIRM THAT |
| INFORMATION REQUIRED BY 103.2.2 IS INCLUDED IN THE |
| PLAN. |
| |
| 28. FBC 2010 603.1, PROVIDE INFORMATION REGARDING THE |
| ACRYLIC FABRIC AND THE VINYL COVERED FENCE. THIS |
| SECTION LISTS THE COMBUSTIBLES PERMITTED IN TYPE I AND |
| II BUILDINGS. COMPLIANCE NOT CLEAR. |
| |
| 29. 2 AE160 AND DETAILS, PENETRATIONS INTO A RATED |
| STAIR SHOULD BE LIMITED TO THOSE REQUIRED FOR THE |
| ENCLOSURE, FBC 1022.4; DRAINS ARE SHOWN. |
| |
| 30. FBC 703, PROVIDE DETAILS FOR THE FIRE RATED |
| STRUCTURAL ELEMENTS TO SHOW COMPLIANCE WITH TYPE 1B |
| BUILDING PER TABLE 601. |
| |
| 31. AE150A AND OTHER SHEETS, UPPER DECK UNDER AWNING |
| PARKING INCLUDES NON ACCESSIBLE SPACES ONLY. SEE FBC |
| 2010 ACCESSIBILITY 103, EQUIVALENT FACILITATION. IT |
| APPEARS THAT EITHER ACCESSIBLE SPACES SHOULD BE |
| INCLUDED UNDER AWNING OR ACCESSIBLE SPACES MOVED TO A |
| COVERED FLOOR. |
| |
| REVISED 8/28/15 - PER ROBERT BROWN, BUILDING OFFICIAL, |
| AS DISCUSSED IN MEETING W/ARCHITECT, IT IS ACCEPTABLE |
| FOR ACCESSIBLE PARKING TO REMAIN AS DESIGNED DUE TO THE |
| NUMBER OF ACCESSIBLE SPACES UNDER COVER ON OTHER |
| FLOORS. |
| |
| 32. FBC 107, DUE TO THE SIZE OF THIS PLAN, IT IS |
| SUGGESTED THAT EITHER THE PLAN BE SUBMITTED DIGITALLY |
| OR THAT THE PLAN SETS BE SPLIT INTO TWO OR THREE ROLLS |
| (ARCH, STRUCTURAL, MEP), FBC 107. |
| |
| WHEN RESUBMITTING, IF THIS REMAINS A PAPER SUBMITTAL |
| RATHER THAN DIGITAL, ALL OLD SHEETS ARE TO BE REMOVED |
| FROM THE BOUND SET AND NEW SHEETS PUT IN THEIR PLACE. |
| THE OLD SHEETS ARE TO BE RETAINED (ALL SETS) AND BOUND |
| SEPARATELY FROM THE NEW SETS. PLEASE DO NOT REMOVE |
| ANYTHING FROM THE DEPARTMENT AS SOMETIMES OLD SHEETS |
| ARE USED TO AVOID RE-STAMPS BY TRADES WHICH HAVE PASSED |
| OR PARTIALLY PASSED. |
| |
| |