2015-06-05 18:30:12RE-ROOF BUILDING REVIEW COMMENTS.
 CODE 2010 FBC
  
 1- FLAT ROOF FLORIDA PRODUCT APPROVAL FL1654-R14
 SUBMITTED:
 A) THE DESIGN PRESSURES FOR THE SELECTED ASSEMBLY
 (W-49) IS -90PSF. THIS BUILDING IS LOCATED IN EXPOSURE
 "C". THE CORNER PRESSURES FOR THIS BUILDING ARE HIGHER
 THAN -90PSF. THIS ASSEMBLY CAN NOT BE USED BECAUSE
 RATIONAL ANALYSIS IS NOT ALLOWED FOR NAIL ENHANCING.
 SEE NOTE #9 ON PAGE 2 OF 33. NEED TO SELECT ANOTHER
 ASSEMBLY THAT MEETS ALL THE DESIGN PRESSURES OR ANOTHER
 ASSEMBLY THAT ALLOWS RATIONAL ANALYSIS (SIGNED AND
 SEALED RAS 117 CALCULATIONS). OR PROVIDE ANOTHER
 PRODUCT APPROVAL. SEC. R301 OF 2010 FBC-RESIDENTIAL.
  
 NOTE: KEEP IN MIND THAT THIS IS A 2 STORY BUILDING.
 NEED TO CONSIDER THIS TO DETERMINE THE DESIGN PRESSURES
 ACCORDING TO THE MEAN ROOF HEIGHT
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]