Plan Review Notes
Plan Review Notes For Permit 15060073
Permit Number 15060073
Review Stop E
Sequence Number 1
Notes
Date Text
2015-06-17 16:23:556/17/2015
 PROJECT: APARTMENT 15-E
 PERMIT#: 15060073
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 SEE BUILDING REVIEW NOTES. COMPLY WITH BUILDING REVIEW
 AND INCLUDE ALL ELECTRICAL ELEMENTS ON NEW PLANS WHEN
 RESUBMITING. IN ADDITION INCLUDE THE FOLLOWING
 ELECTRICAL ELEMENTS IN THE NEW PLANS PER THE 2010
 FLORIDA BUILDING CODE AND THE 2008 NATIONAL ELECTRICAL
 CODE.
  
 1) FBC-RESIDENTIAL 314 AND 315. ADD SMOKE DETECTORS AS
 REQUIRED FOR NEW CONSTRCTION.: WHEN ALTERATIONS,
 REPAIRS, OR ADDITIONS REQUIRING A PERMIT OCCUR, OR WHEN
 ONE OR MORE SLEEPING ROOMS ARE ADDED OR CREATED IN
 EXISTING DWELLINGS, THE INDIVIDUAL DWELLING UNIT SHALL
 BE EQUIPPED WITH SMOKE ALARMS LOCATED AS REQUIRED FOR
 NEW DWELLINGS.
  
 2) NEC 210.12, 406.11ALL NEW GENERAL PURPOSE OUTLETS
 MUST BE TAMPER RESISTANT AND AFCI PROTECTED.
  
 3) NEC 210.52(C)(3) BATHROOM BRANCH CIRCUITS. IN
 ADDITION TO THE NUMBER OF BRANCH CIRCUITS REQUIRED BY
 OTHER PARTS OF THIS SECTION, AT LEAST ONE 20-AMPERE
 BRANCH CIRCUIT SHALL BE PROVIDED TO SUPPLY BATHROOM
 RECEPTACLE OUTLET(S). SUCH CIRCUITS SHALL HAVE NO OTHER
 OUTLETS.
 3A) NEC 210.52 (D) BATHROOMS. IN DWELLING UNITS, AT
 LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED IN
 BATHROOMS WITHIN (3 FT) OF THE OUTSIDE EDGE OF EACH
 BASIN.
 3(B) NEC 210.8.(A) ALL 125-VOLT, SINGLE-PHASE, 15- AND
 20-AMPERE RECEPTACLES INSTALLED IN THE LOCATIONS
 SPECIFIED IN (1) THROUGH (8) SHALL HAVE GROUND-FAULT
 CIRCUIT-INTERRUPTER PROTECTION FOR PERSONNEL. (1)
 BATHROOMS.
  
 4) NEC 210.52(C)(1) WALL COUNTERTOP SPACES. A
 RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH WALL
 COUNTERTOP SPACE THAT IS 300 MM (12 IN.) OR WIDER.
  
 5) FBC-E 502.3.8 RECESSED LIGHTING. RECESSED LUMINAIRES
 INSTALLED IN THE BUILDING THERMAL ENVELOPE SHALL BE IC
 AND AIR TIGHT RATED AND SEALED TO LIMIT AIR LEAKAGE
 BETWEEN CONDITIONED AND UNCONDITIONED SPACES.
  
 6) NEC 408.4 PROVIDE A PANEL SCHEDULE. EVERY CIRCUIT
 AND CIRCUIT MODIFICATION SHALL BE LEGIBLY IDENTIFIED AS
 TO ITS CLEAR, EVIDENT, AND SPECIFIC PURPOSE OR USE.
  
 7) NEC 220.16 LOADS FOR NEW CIRCUITS OR EXTENDED
 CIRCUITS IN PREVIOUSLY WIRED DWELLING UNITS SHALL BE
 CALCULATED IN ACCORDANCE WITH EITHER 220.12 OR 220.14,
 AS APPLICABLE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  