2015-06-17 16:23:55 | 6/17/2015 |
| PROJECT: APARTMENT 15-E |
| PERMIT#: 15060073 |
| CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| 1ST ELECTRICAL PLAN REVIEW |
| ACTION: DENIED |
| |
| SEE BUILDING REVIEW NOTES. COMPLY WITH BUILDING REVIEW |
| AND INCLUDE ALL ELECTRICAL ELEMENTS ON NEW PLANS WHEN |
| RESUBMITING. IN ADDITION INCLUDE THE FOLLOWING |
| ELECTRICAL ELEMENTS IN THE NEW PLANS PER THE 2010 |
| FLORIDA BUILDING CODE AND THE 2008 NATIONAL ELECTRICAL |
| CODE. |
| |
| 1) FBC-RESIDENTIAL 314 AND 315. ADD SMOKE DETECTORS AS |
| REQUIRED FOR NEW CONSTRCTION.: WHEN ALTERATIONS, |
| REPAIRS, OR ADDITIONS REQUIRING A PERMIT OCCUR, OR WHEN |
| ONE OR MORE SLEEPING ROOMS ARE ADDED OR CREATED IN |
| EXISTING DWELLINGS, THE INDIVIDUAL DWELLING UNIT SHALL |
| BE EQUIPPED WITH SMOKE ALARMS LOCATED AS REQUIRED FOR |
| NEW DWELLINGS. |
| |
| 2) NEC 210.12, 406.11ALL NEW GENERAL PURPOSE OUTLETS |
| MUST BE TAMPER RESISTANT AND AFCI PROTECTED. |
| |
| 3) NEC 210.52(C)(3) BATHROOM BRANCH CIRCUITS. IN |
| ADDITION TO THE NUMBER OF BRANCH CIRCUITS REQUIRED BY |
| OTHER PARTS OF THIS SECTION, AT LEAST ONE 20-AMPERE |
| BRANCH CIRCUIT SHALL BE PROVIDED TO SUPPLY BATHROOM |
| RECEPTACLE OUTLET(S). SUCH CIRCUITS SHALL HAVE NO OTHER |
| OUTLETS. |
| 3A) NEC 210.52 (D) BATHROOMS. IN DWELLING UNITS, AT |
| LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED IN |
| BATHROOMS WITHIN (3 FT) OF THE OUTSIDE EDGE OF EACH |
| BASIN. |
| 3(B) NEC 210.8.(A) ALL 125-VOLT, SINGLE-PHASE, 15- AND |
| 20-AMPERE RECEPTACLES INSTALLED IN THE LOCATIONS |
| SPECIFIED IN (1) THROUGH (8) SHALL HAVE GROUND-FAULT |
| CIRCUIT-INTERRUPTER PROTECTION FOR PERSONNEL. (1) |
| BATHROOMS. |
| |
| 4) NEC 210.52(C)(1) WALL COUNTERTOP SPACES. A |
| RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH WALL |
| COUNTERTOP SPACE THAT IS 300 MM (12 IN.) OR WIDER. |
| |
| 5) FBC-E 502.3.8 RECESSED LIGHTING. RECESSED LUMINAIRES |
| INSTALLED IN THE BUILDING THERMAL ENVELOPE SHALL BE IC |
| AND AIR TIGHT RATED AND SEALED TO LIMIT AIR LEAKAGE |
| BETWEEN CONDITIONED AND UNCONDITIONED SPACES. |
| |
| 6) NEC 408.4 PROVIDE A PANEL SCHEDULE. EVERY CIRCUIT |
| AND CIRCUIT MODIFICATION SHALL BE LEGIBLY IDENTIFIED AS |
| TO ITS CLEAR, EVIDENT, AND SPECIFIC PURPOSE OR USE. |
| |
| 7) NEC 220.16 LOADS FOR NEW CIRCUITS OR EXTENDED |
| CIRCUITS IN PREVIOUSLY WIRED DWELLING UNITS SHALL BE |
| CALCULATED IN ACCORDANCE WITH EITHER 220.12 OR 220.14, |
| AS APPLICABLE. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. SEE LINK: |
| HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| |
| ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| REVIEW. |
| DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |