2015-06-10 07:47:07 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 15060073 |
| ADD: 529 S. FLAGLER DR. SUITE # 15E |
| CONT: CAMBRIDGE CONSTRUCTION |
| TEL: ( 561)784-3722 |
| E-MAIL: [email protected] |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: WED. JUNE 10/ 2015 |
| ACTION: DENIED |
| |
| 1) AN ITEMIZED LIST OF PROPOSED WORK WAS SUBMITTED, NO |
| PLANS SHOWING THE AREA AND DESCRIPTION OF WORK TO BE |
| COMPLETED WITHIN THIS PROJECT. |
| |
| 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| CODE, CHAPTER 1, ADMINISTRATION, 2010 107.2.1.3 |
| ADDITIONAL DATA. THE BUILDING OFFICIAL MAY REQUIRE |
| DETAILS, COMPUTATIONS, STRESS DIAGRAMS, AND OTHER DATA |
| NECESSARY TO DESCRIBE THE CONSTRUCTION OR INSTALLATION |
| AND THE BASIS OF CALCULATIONS. ALL DRAWINGS, |
| SPECIFICATIONS AND ACCOMPANYING DATA REQUIRED BY THE |
| BUILDING OFFICIAL TO BE PREPARED BY AN ARCHITECT OR |
| ENGINEER SHALL BE AFFIXED WITH THEIR OFFICIAL SEAL, |
| SIGNATURE AND DATE AS STATE LAW REQUIRES. |
| |
| 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING PLANS |
| SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON |
| SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM. |
| THE BUILDING OFFICIAL MAY ESTABLISH THROUGH |
| DEPARTMENTAL POLICY, OTHER STANDARDS FOR PLANS AND |
| SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS |
| RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE SUCH |
| THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR |
| OTHER ITEMS RELATED TO RECORDS |
| MANAGEMENT. |
| |
| 107.3.5 107.3.5.1 COMMERCIAL BUILDINGS. MINIMUM PLAN |
| REVIEW CRITERIA FOR BUILDINGS. THE EXAMINATION OF THE |
| DOCUMENTS BY THE BUILDING OFFICIAL SHALL INCLUDE THE |
| FOLLOWING MINIMUM CRITERIA AND DOCUMENTS: |
| 107.3.5.1.1 BUILDING |
| A FLOOR PLAN |
| OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS |
| SHALL BE DETERMINED. |
| MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED (SEE |
| TABLE 503). |
| FIRE-RESISTANT CONSTRUCTION REQUIREMENTS SHALL INCLUDE |
| THE FOLLOWING COMPONENTS: |
| FIRE-RESISTANT SEPARATIONS |
| FIRE-RESISTANT PROTECTION FOR TYPE OF CONSTRUCTION |
| PROTECTION OF OPENINGS AND PENETRATIONS OF RATED WALLS |
| FIRE SUPPRESSION SYSTEMS SHALL INCLUDE: SCHEMATIC FIRE |
| SPRINKLERS |
| STRUCTURAL REQUIREMENTS SHALL INCLUDE: DROPPED CEILINGS |
| AND SOFFIT DESIGN AND ATTACHMENT. |
| INTERIOR REQUIREMENTS SHALL INCLUDE THE FOLLOWING: |
| INTERIOR FINISHES (FLAME SPREAD/SMOKE DEVELOPMENT) |
| LIGHT AND VENTILATION |
| SANITATION: TYPE OF TILE BACKING MATERIAL |
| SOUND PROOFING OF TENANT WALLS AND FLOOR SYSTEMS. |
| |
| 2) BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION: NOTE |
| PROTECTO WRAP MEETS ALL THREE OF THE ASTM TEST, MISSING |
| FROM THE REPORTS IS THE FLAME SPREAD INDEX TESTING |
| REPORT. |
| |
| 2A) FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND. |
| FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| |
| 2B) FBC-B 2010 1207.2 1207.2 AIR-BORNE SOUND. |
| WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| E 90. |
| |
| 2C) FLAME SPREAD- FBC-B 2010 603.1.2 EXCEPTION 2. |
| INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| |
| FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| |
| 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| THIS REVIEW. |
| |