Plan Review Notes For Permit 15060070 |
Permit Number |
15060070 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-06-06 07:35:36 | PLAN DENIED | | 1) REFER TO SECTION 601.4 BALANCED RETURN AIR | | 2010 FBC (M) | | 2) PROVIDE CFM ON SUPPLY DROPS. SECTION 107 | | 2010 FBC | | 3) REFER TO SECTION 606.2.1 SUPPLY AIR | | 2010 FBC (M) | | 4) PROVIDE MANUFACTURES INSTALLATION INSTRUCTIONS | | ON AIRCONDITIONING EQUIPMENT FOR NEXT REVIEW | | PER SECTION 304.1 GENERAL. 2010 FBC (M | | | | PLAN REVIEW BY HAROLD MOSER | | [email protected] | | OFFICE 561-805-6732 | | FAX 561-805-6676 |
|