Plan Review Notes
Plan Review Notes For Permit 15060041
Permit Number 15060041
Review Stop G
Sequence Number 1
Notes
Date Text
2015-06-04 06:07:541) RE-CHECK THE BTU LOAD ON THE SYSTEM. MY CALCULATIONS
 ARRIVE AT 269 BTU'S YET THE PLANS NOTE 330 BTU'S.
 CLARIFY.
 2) IF 330 BTU'S IS CORRECT, THE MINIMUM PIPE SIZE FROM
 THE METER SHALL BE 1 1/4" PER 2010 FBC-R TABLE G2413.4
 (1).
 3) SUBMIT TWO COPIES OF A FLOOR PLAN SHOWING THE
 LOCATION OF ALL APPLIANCES.WPB AMEND. TO FBC SEC.
 107.2.1.
 4) ALL GAS APPLIANCES SHALL BE LISTED AND LABELED PER
 THE 2010 FBCR SEC.G2404.3. SUBMIT 2 COPIES OF MANUF.
 SPEC. SHEETS FOR EACH APPLIANCE THAT SHOWS EACH
 APPLIANCE HAS A LISTING FROM A NATIONALLY RECOGNIZED
 LISTING AGENCY.
 5) IF THE TANKLESS WATER HEATER IS NOT A DIRECT VENT
 APPLIANCE, SUBMIT CALCULATIONS FOR COMBUSTION AIR PER
 FBCR SEC.G2407.
  