2015-06-04 06:07:54 | 1) RE-CHECK THE BTU LOAD ON THE SYSTEM. MY CALCULATIONS | | ARRIVE AT 269 BTU'S YET THE PLANS NOTE 330 BTU'S. | | CLARIFY. | | 2) IF 330 BTU'S IS CORRECT, THE MINIMUM PIPE SIZE FROM | | THE METER SHALL BE 1 1/4" PER 2010 FBC-R TABLE G2413.4 | | (1). | | 3) SUBMIT TWO COPIES OF A FLOOR PLAN SHOWING THE | | LOCATION OF ALL APPLIANCES.WPB AMEND. TO FBC SEC. | | 107.2.1. | | 4) ALL GAS APPLIANCES SHALL BE LISTED AND LABELED PER | | THE 2010 FBCR SEC.G2404.3. SUBMIT 2 COPIES OF MANUF. | | SPEC. SHEETS FOR EACH APPLIANCE THAT SHOWS EACH | | APPLIANCE HAS A LISTING FROM A NATIONALLY RECOGNIZED | | LISTING AGENCY. | | 5) IF THE TANKLESS WATER HEATER IS NOT A DIRECT VENT | | APPLIANCE, SUBMIT CALCULATIONS FOR COMBUSTION AIR PER | | FBCR SEC.G2407. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | |
|