Notes
Date Text
2015-06-16 06:15:231) SHOW THE LENGTH AND WIDTH DIMENSIONS OF BOTH TOILET
 ROOMS. THE MINIMUM WIDTH OF THE TOILET ROOMS SHALL BE
 85 INCHES WHEN ALL THE PLUMBING FIXTURES ARE LOCATED ON
 THE SAME WALL. 86 INCHES IN WIDTH ALLOWS FOR
 CONSTRUCTION TOLERANCES.WPB AMEND. TO FBC SEC. 107.2.1.
 2) THE BREAKROOM SINK SHALL COMPLY WITH THE FL. ACCESS.
 CODE SECS. 212, 606, 804.
 3) THE MAXIMUM HEIGHT OF THE COUNTER OF THE BREAK ROOM
 SINK SHALL BE AT 34 INCHES ABOVE FINISH FLOOR.
 FBC-ACCESSIBILITY SECC.606.3.
 4) SUBMIT A WATER RISER FOR BOTH TOILET ROOMS. WPB
 AMEND. TO FBC SEC. 107.3.5.1.3.
 5) CLEANOUTS ARE REQD. IN THE WASTE STACKS PER 2010
 FBC-PLUMBING, SEC.708.3.4.
 6) SHT.A-3 - PLUMBING NOTES # 1 & # 8 REFER TO THE 2007
 FLORIDA PLUMBING CODE. REVISE NOTES TO REFER TO 2010
 FPC.
 7) THE LAYOUT/LOCATION OF THE PLUMBING FIXTURES ON THE
 SANITARY RISER DOES NOT CORRELATE WITH THE FLOOR PLAN.
 WPB AMEND. TO FBC SEC. 107.2.1.
 8) IDENTIFY THE WASTE STACK FOR THE BREAK ROOM SINK.
 BOTH STACKS ARE LABELED AS A LAVATORY.
  