Plan Review Notes
Plan Review Notes For Permit 15051296
Permit Number 15051296
Review Stop M
Sequence Number 1
Notes
Date Text
2015-07-08 07:41:281ST REVIEW: FBC 2010 MECHANICAL
  
 1) PROVIDE COOLING AND HEATING LOAD CALCULATIONS FOR
 THE PROPOSED AC SYSTEM IN ACCORDANCE WITH ACCA MANUAL N
 OR THE ACCA/ASHRAE STANDARD 183- SECTION 503.2.1 FBC-10
 ENERGY CONSERVATION.
 2) SHEET A3: THE PLAN IS INDICATING THE AREA ABOVE THE
 CEILING IS A RETURN AIR PLENUM. REFERENCE SECTION
 602.2.1 AND ALL APPLICABLE SUB-SECTIONS PERTAINING TO
 NON-COMBUSTIBLE AND OTHER MATERIALS PERMITTED TO BE
 INSTALLED IN THE PLENUM. PLEASE PLACE NOTES ON THE PLAN
 TO VERIFY COMPLIANCE.
 3) A3: INDICATE THE TYPE AND SIZE OF CONDENSATE PIPING
 AND CLARIFY THE DISCHARGE LOCATION- SECTION 307. THERE
 IS A NOTE ON THE PLAN STATING "PROVIDE COND. TO WET
 COL.": PLEASE CLARIFY IF THIS IS AN EXISTING STORM
 DRAIN RISER.
 4) A3: PROVIDE UPDATED WIND LOAD TIE-DOWN ENGINEERING
 FOR ANCHORING THE CONDENSER TO THE PAD. THE DETAIL ON
 THE PLAN IS INDICATING A WIND SPEED OF 120 MPH.
 REFERENCE SECTION 301.12 FBC-10 MECHANICAL, AND SECTION
 1609 FBC-10 BUILDING. THE ULTIMATE DESIGN WIND SPEED
 FOR RISK CATEGORY II IN WEST PALM BEACH IS 170 MPH- SEE
 FIGURE 1609A. REVISE THE DETAIL ACCORDINGLY AND
 INDICATE THE TYPE, SIZE, AND GAGE OF STEEL HURRICANE
 STRAPS TO BE INSTALLED.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  