Plan Review Notes For Permit 15051289 |
Permit Number |
15051289 |
|
Review Stop |
B |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2015-10-16 15:07:52 | PLAN | | REVIEW COMMENTS | | | | 3RD REVIEW: FBC 2010 | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THE ENERGY FORM DOES NOT SHOW COMPLIANCE WITH FBC | | ENERGY CONSERVATION SECTION 402. THE U-FACTOR SPECIFIED | | IS MORE THAN THE MAXIMUM OF .65. THE PERCENTAGE OF | | GLASS TO FLOOR AREA IS NOT 20 PERCENT. THE RAISED FLOOR | | AREA IS SPECIFIED AS 56 SQFT AND THE ENCLOSED AREA IS | | 177 SQFT. THE AHU LOCATION IS NOT LISTED ON THE FORM. | | THE FORM IS NOT SIGNED BY THE OWNER/AGENT. YOU WILL | | NEED TO SUBMIT DOCUMENTATION FOR THE WINDOWS THAT WILL | | BE INSTALLED TO SHOW THEIR U-FACTOR AND SHGC. | | | | 2) ONE SET OF THE PLANS WAS SIGNED OUT AND NOT | | RETURNED. TWO SETS OF PLANS ARE REQUIRED FOR REVIEW. | | FBC 107.1 | | | | 3) AN IMPACT FEE REVIEW BY PALM BEACH COUNTY IS | | REQUIRED. | | | | 4) IN ORDER TO REDUCE PLAN REVIEW TIMES AND PROVIDE | | CLARIFICATION, PLEASE SUBMIT A RESPONSE LETTER | | INDICATING HOW EACH OF THE REVIEW COMMENTS HAS BEEN | | ADDRESSED. | | | | |
|