2015-10-16 15:07:52PLAN
 REVIEW COMMENTS
  
 3RD REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE ENERGY FORM DOES NOT SHOW COMPLIANCE WITH FBC
 ENERGY CONSERVATION SECTION 402. THE U-FACTOR SPECIFIED
 IS MORE THAN THE MAXIMUM OF .65. THE PERCENTAGE OF
 GLASS TO FLOOR AREA IS NOT 20 PERCENT. THE RAISED FLOOR
 AREA IS SPECIFIED AS 56 SQFT AND THE ENCLOSED AREA IS
 177 SQFT. THE AHU LOCATION IS NOT LISTED ON THE FORM.
 THE FORM IS NOT SIGNED BY THE OWNER/AGENT. YOU WILL
 NEED TO SUBMIT DOCUMENTATION FOR THE WINDOWS THAT WILL
 BE INSTALLED TO SHOW THEIR U-FACTOR AND SHGC.
  
 2) ONE SET OF THE PLANS WAS SIGNED OUT AND NOT
 RETURNED. TWO SETS OF PLANS ARE REQUIRED FOR REVIEW.
 FBC 107.1
  
 3) AN IMPACT FEE REVIEW BY PALM BEACH COUNTY IS
 REQUIRED.
  
 4) IN ORDER TO REDUCE PLAN REVIEW TIMES AND PROVIDE
 CLARIFICATION, PLEASE SUBMIT A RESPONSE LETTER
 INDICATING HOW EACH OF THE REVIEW COMMENTS HAS BEEN
 ADDRESSED.
  
  