Plan Review Notes
Plan Review Notes For Permit 15051289
Permit Number 15051289
Review Stop B
Sequence Number 2
Notes
Date Text
2015-09-10 19:10:58PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE ENERGY FORM DOES NOT SHOW COMPLIANCE WITH FBC
 ENERGY CONSERVATION SECTION 402. THE U-FACTOR SPECIFIED
 IS MORE THAN THE MAXIMUM OF .65. THE PERCENTAGE OF
 GLASS TO FLOOR AREA IS NOT 20 PERCENT. THE RAISED FLOOR
 AREA IS SPECIFIED AS 56 SQFT AND THE ENCLOSED AREA IS
 177 SQFT. THE AHU LOCATION IS NOT LISTED ON THE FORM.
 THE FORM IS NOT SIGNED BY THE OWNER/AGENT. YOU WILL
 NEED TO SUBMIT DOCUMENTATION FOR THE WINDOWS THAT WILL
 BE INSTALLED TO SHOW THEIR U-FACTOR AND SHGC.
  
 2) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE NEW
 WINDOWS THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING
 BY THE DESIGNER OF RECORD. FBC107.3.4.1
  
 3) SHOW THAT THE WINDOWS WILL COMPLY WITH R301.2.1.2
 PROTECTION OF OPENINGS. WINDOWS IN BUILDINGS LOCATED IN
 WINDBORNE DEBRIS REGIONS SHALL HAVE GLAZED OPENINGS
 PROTECTED FROM WINDBORNE DEBRIS. GLAZED OPENING
 PROTECTION FOR WINDBORNE DEBRIS SHALL MEET THE
 REQUIREMENTS OF THE LARGE MISSILE TEST OF ASTM E 1996,
 ASTM E 1886, SSTD 12 OR TAS 201,202 AND 203 OR AAMA 506
 REFERENCED THEREIN. ( IF USING STORM PANELS, SUBMIT
 PRODUCT APPROVALS AND AN INSTALLATION SCHEDULE. )
  
 4) THE VALUE OF $10,000.00 ON THE APPLICATION FOR THE
 SCOPE OF WORK SHOWN ON THE PLANS APPEARS TO
 UNDERVALUED. SUBMIT A COPY OF THE SIGNED CONTRACT. FBC
 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. SUBMIT
 A COPY OF THE SIGNED CONTRACT TO VERIFY THE VALUATION
 OF THE PROJECT.
  
 5) IN ORDER TO REDUCE PLAN REVIEW TIMES AND PROVIDE
 CLARIFICATION, PLEASE SUBMIT A RESPONSE LETTER
 INDICATING HOW EACH OF THE REVIEW COMMENTS HAS BEEN
 ADDRESSED.
  
  