Plan Review Notes For Permit 15051289 |
Permit Number |
15051289 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-05-30 14:58:21 | APPROVED WITH EXCEPTION. THE PLANS HAVE BEEN APPROVED | | PROVISIONALLY. FAILURE TO CORRECT THE LISTED | | DEFICIENCIES PRIOR TO INSPECTION WILL RESULT IN FAILED | | INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION | | FEE(S). | | | | 1) ALL NEW GENERAL PURPOSE OUTLETS SHALL BE AFCI | | PROTECTED. NEC 210.12 | | | | 2) ALL NEW RECEPTACLESSHALL BE TAMPER RESISTANT. NEC | | 406.11 | | | | 3) PROVIDE A 20 AMPERE BRANCH CIRCUIT FOR THE | | BATHROOM(S). NEC 210.11 (C) | | | | 4) VERIFY OR INSTALL INTERCONNECTED SMOKE DETECTORS. | | FBC R314, 315 | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | 561-805-6717 OR [email protected] |
|