Plan Review Notes
Plan Review Notes For Permit 15051289
Permit Number 15051289
Review Stop E
Sequence Number 1
Notes
Date Text
2015-05-30 14:58:21APPROVED WITH EXCEPTION. THE PLANS HAVE BEEN APPROVED
 PROVISIONALLY. FAILURE TO CORRECT THE LISTED
 DEFICIENCIES PRIOR TO INSPECTION WILL RESULT IN FAILED
 INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION
 FEE(S).
  
 1) ALL NEW GENERAL PURPOSE OUTLETS SHALL BE AFCI
 PROTECTED. NEC 210.12
  
 2) ALL NEW RECEPTACLESSHALL BE TAMPER RESISTANT. NEC
 406.11
  
 3) PROVIDE A 20 AMPERE BRANCH CIRCUIT FOR THE
 BATHROOM(S). NEC 210.11 (C)
  
 4) VERIFY OR INSTALL INTERCONNECTED SMOKE DETECTORS.
 FBC R314, 315
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]