2015-08-13 14:38:44PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC-R314.3.1 ALTERATIONS, REPAIRS AND ADDITIONS.
 WHEN ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS.
  
 2) SUBMIT ENERGY CALCULATIONS AS REQUIRED BY FBC ENERGY
 CONSERVATION SECTION 401.2.
  
 3) PROVIDE A FRAMING DETAIL FOR THE EXTERIOR IN-FILL
 WALLS THAT SHOWS THE FRAMING CONNECTORS / STRAPS AND
 THE WINDOW OPENING FRAMING. FBC 107.2.1 AND FBC-R601.2
  
 4) FBC 107.3.5.3 - PROVIDE COMPONENT AND CLADDING
 DESIGN PRESSURES PURSUANT TO FBC-R301.2 FOR THE SINGLE
 HUNG WINDOWS IN THE NEW SITTING ROOM.
  
 5) SPECIFY THE CEILING INSULATION TYPE AND R-VALUE ON
 THE PLANS FOR THE NEW SITTING ROOM. FBC ENERGY
 CONSERVATION 401.2
  
 6) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3
 THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. PROVIDE TWO COMPLETE PRODUCT
 APPROVALS WITH FL OR NOA NUMBERS INCLUDING INSTALLATION
 INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES FOR THE NEW
 WINDOW SINGLE HUNG WINDOWS.
  
 7) SHOW COMPLIANCE WITH FBC-R 301.2.1.2 FOR LARGE
 MISSILE IMPACT PROTECTION AT THE NEW WINDOWS.
  
 8) IF THE NEW WINDOWS ARE NOT RATED FOR LARGE MISSILE
 IMPACT, THEN FBC - R 301.2.1.2 SUBMIT TWO COPIES OF AN
 INSTALLATION SCHEDULE AND KEY PLAN FOR THE STORM
 PANELS. SPECIFY THE OPENING SIZE, THE WIND PRESSURES,
 TYPE OF ANCHOR, ANCHOR SPACING, EDGE DISTANCE, PANEL
 LENGTH, PANEL SPAN, SEPARATION DISTANCE FROM PANEL TO
 GLASS AND THE APPLICABLE SECTION NUMBER FROM THE
 INSTALLATION DRAWINGS. I HAVE INCLUDED A LINK TO THE
 CONSTRUCTION SERVICES DEPARTMENT SITE THAT HAS MANY OF
 THE RELATED FORMS INCLUDING
 THE SCHEDULE FOR INSTALLATION OF OPENING PROTECTIVE
 DEVICES.
 HTTP://WPB.ORG/DEVELOPMENT/FORMS-AND-PUBLICATIONS/
  
 9) THE VALUE OF $10,000.00 ON THE APPLICATION FOR THE
 SCOPE OF WORK SHOWN ON THE PLANS APPEARS TO
 UNDERVALUED. SUBMIT A COPY OF THE SIGNED CONTRACT. FBC
 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
  