Plan Review Notes For Permit 15051267 |
Permit Number |
15051267 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-06-26 10:05:49 | APPROVED WITH EXCEPTION. THE PLANS HAVE BEEN APPROVED | | PROVISIONALLY. FAILURE TO CORRECT THE LISTED | | DEFICIENCIES PRIOR TO INSPECTION WILL RESULT IN FAILED | | INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION | | FEE(S). | | | | 1) 702.5 (A) AVAILABLE | | SHORT-CIRCUIT CURRENT. OPTIONAL STANDBY SYSTEM | | EQUIPMENT SHALL BE SUITABLE FOR THE MAXIMUM AVAILABLE | | SHORT-CIRCUIT CURRENT AT ITS TERMINALS. | | | | 2) NEC 702.8 SIGNS.(A) STANDBY. | | A SIGN SHALL BE PLACED AT THE SERVICE-ENTRANCE | | EQUIPMENT THAT INDICATES THE TYPE AND LOCATION OF | | ON-SITE OPTIONAL STANDBY POWER SOURCES. A SIGN SHALL | | NOT BE REQUIRED FOR INDIVIDUAL UNIT EQUIPMENT FOR | | STANDBY ILLUMINATION. | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | 561-805-6717 OR [email protected] | | |
|