Plan Review Notes For Permit 15051260 |
Permit Number |
15051260 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-06-17 03:47:09 | 1) A DRINKING FOUNTAIN IS REQUIRED IN THIS SPACE PER | | TABLE 403.1 OF THE 2010 FBC-PLUMBING. A MINIMUM OF 2 | | DRINKING FOUNTAINS ARE REQUIRED PER TABLE 403.1, | | FOOTNOTE # E AND FBC-ACCESSIBILITY SEC.211.2. | | 2) SHT. A2.3 - ELEVATION # J - THE GRAB BAR BEHIND THE | | WATER CLOSET SHALL COMPLY WITH 2010 FBC-ACCESSIBILITY, | | SEC.604.5.2 FOR SPACING REQS. | | 3) THE HEIGHT OF THE GRAB BARS SHALL BE MEASURED FROM | | THE FINISH FLOOR TO THE TOP OF THE GRIPPING SURFACE PER | | 2010 FBC- ACCESSIBILITY, SEC.609.4. | | 4) THE HEATER PAN SHALL COMPLY WITH THE 2010 | | FBC-PLUMBING, SEC.504.7. | | 5) SUBMIT DETAILS FOR THE WATER HEATER SUPPORT. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | | | |
|