2015-06-17 03:47:091) A DRINKING FOUNTAIN IS REQUIRED IN THIS SPACE PER
 TABLE 403.1 OF THE 2010 FBC-PLUMBING. A MINIMUM OF 2
 DRINKING FOUNTAINS ARE REQUIRED PER TABLE 403.1,
 FOOTNOTE # E AND FBC-ACCESSIBILITY SEC.211.2.
 2) SHT. A2.3 - ELEVATION # J - THE GRAB BAR BEHIND THE
 WATER CLOSET SHALL COMPLY WITH 2010 FBC-ACCESSIBILITY,
 SEC.604.5.2 FOR SPACING REQS.
 3) THE HEIGHT OF THE GRAB BARS SHALL BE MEASURED FROM
 THE FINISH FLOOR TO THE TOP OF THE GRIPPING SURFACE PER
 2010 FBC- ACCESSIBILITY, SEC.609.4.
 4) THE HEATER PAN SHALL COMPLY WITH THE 2010
 FBC-PLUMBING, SEC.504.7.
 5) SUBMIT DETAILS FOR THE WATER HEATER SUPPORT.
  