Plan Review Notes For Permit 15051220 |
Permit Number |
15051220 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2015-06-29 08:34:16 | APPROVED WITH EXCEPTION. THE PLANS HAVE BEEN APPROVED | | PROVISIONALLY. FAILURE TO CORRECT THE LISTED | | DEFICIENCIES PRIOR TO INSPECTION WILL RESULT IN FAILED | | INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION | | FEE(S). | | | | 1) NEC 430.102 (B) MOTOR. | | A DISCONNECTING MEANS SHALL BE PROVIDED FOR A MOTOR IN | | ACCORDANCE WITH (B)(1) OR (B)(2). | | (1) A DISCONNECTING MEANS FOR THE MOTOR SHALL BE | | LOCATED IN SIGHT FROM THE MOTOR LOCATION AND THE DRIVEN | | MACHINERY LOCATION. | | EXCEPTION: THE DISCONNECTING MEANS FOR THE MOTOR SHALL | | NOT BE REQUIRED PROVIDED THE CONTROLLER DISCONNECT IS | | INDIVIDUALLY CAPABLE OF BEING LOCKED IN THE OPEN | | POSITION AND SHALL REMAIN IN PLACE WITH OR WITHOUT THE | | LOCK INSTALLED. | | | | 2) NEC 110.22 (A) | | EACH DISCONNECTING MEANS SHALL BE LEGIBLY MARKED TO | | INDICATE ITS PURPOSE UNLESS LOCATED AND ARRANGED SO THE | | PURPOSE IS EVIDENT. THE MARKING SHALL BE OF SUFFICIENT | | DURABILITY TO WITHSTAND THE ENVIRONMENT INVOLVED. | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | 561-805-6717 OR [email protected] |
|