Plan Review Notes
Plan Review Notes For Permit 15051220
Permit Number 15051220
Review Stop E
Sequence Number 2
Notes
Date Text
2015-06-29 08:34:16APPROVED WITH EXCEPTION. THE PLANS HAVE BEEN APPROVED
 PROVISIONALLY. FAILURE TO CORRECT THE LISTED
 DEFICIENCIES PRIOR TO INSPECTION WILL RESULT IN FAILED
 INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION
 FEE(S).
  
 1) NEC 430.102 (B) MOTOR.
 A DISCONNECTING MEANS SHALL BE PROVIDED FOR A MOTOR IN
 ACCORDANCE WITH (B)(1) OR (B)(2).
 (1) A DISCONNECTING MEANS FOR THE MOTOR SHALL BE
 LOCATED IN SIGHT FROM THE MOTOR LOCATION AND THE DRIVEN
 MACHINERY LOCATION.
 EXCEPTION: THE DISCONNECTING MEANS FOR THE MOTOR SHALL
 NOT BE REQUIRED PROVIDED THE CONTROLLER DISCONNECT IS
 INDIVIDUALLY CAPABLE OF BEING LOCKED IN THE OPEN
 POSITION AND SHALL REMAIN IN PLACE WITH OR WITHOUT THE
 LOCK INSTALLED.
  
 2) NEC 110.22 (A)
 EACH DISCONNECTING MEANS SHALL BE LEGIBLY MARKED TO
 INDICATE ITS PURPOSE UNLESS LOCATED AND ARRANGED SO THE
 PURPOSE IS EVIDENT. THE MARKING SHALL BE OF SUFFICIENT
 DURABILITY TO WITHSTAND THE ENVIRONMENT INVOLVED.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]