2015-05-30 14:20:285/30/2015
 PROJECT: FOUNTAIN ELECTRIC
 PERMIT#: 15051220
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW
 COMMENTS:
  
 1) PROVIDE A SITE PLAN AND INDICATE THE LOCATION OF
 PANEL RACK AND FOUNTAIN. FBC 107.2.1
  
 2) PROVIDE A PANEL SCHEDULE INCLUDING ALL OCPD AND WIRE
 SIZES. EVERY CIRCUIT AND CIRCUIT MODIFICATION SHALL BE
 LEGIBLY IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND
 SPECIFIC PURPOSE OR USE. NEC 408.4
  
 3) INDICATE ALL WIRE AND CONDIUT SIZES ON RISER
 DIAGRAM. WPB AMENDMENTS FBC 107.3.5.1.2
  
 4) INDICATE SYSTEM AND OPERATING VOLTAGE ON RISER
 DIAGRAM. WPB AMENDMENTS FBC 107.3.5.1.2
  
 5) VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS
 HAS A FAULT CURRENT RATING THAT IS SUFFICIENT AT
 NOMINAL CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE
 INTERRUPTED. NEC 110.9
  
 6) PROVIDE MANUFACTURER PRODUCT DATA SHEETS INDICATING
 THE TYPE OF OPERATION AND TYPE OF FOUNTAIN.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.