| PROJECT: WESMINSTER RESIDENCE |
| PERMIT#: 15051158 |
| CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| 1ST ELECTRICAL PLAN REVIEW |
| ACTION: DENIED |
| |
| REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW |
| COMMENTS: |
| |
| 1) THE ELECTRICAL PLAN INDIACTES VIA NOTES ON A.01 THAT |
| THE ELECTRICAL PANEL CERTAIN LIGHTING AND SMOKE |
| DETECTORS WILL REMAIN FOR THE DURATION OF THE |
| CONSTRUCTION PROCESS. INDICATE THE LOCATION OF THE |
| ELECTRICAL PANEL, ELECTRICAL SERVICE, LIGHTING AND |
| SMOKE DETECTORS THAT ARE EXISTING TO REMAIN. |
| |
| 2) PROVIDE A PANEL SCHEDULE FOR CIRCUITS THAT WILL |
| REMAIN. NEC 408.4 |
| |
| 3) INDICATE THE LOCATION OF THE REQUIRED GFI |
| RECEPTACLES FOR CONSTRUCTION. NEC 590.6 |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. SEE LINK: |
| HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| |
| ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| REVIEW. |