Plan Review Notes
Plan Review Notes For Permit 15051158
Permit Number 15051158
Review Stop E
Sequence Number 1
Notes
Date Text
2015-06-05 11:09:466/5/2015
 PROJECT: WESMINSTER RESIDENCE
 PERMIT#: 15051158
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW
 COMMENTS:
  
 1) THE ELECTRICAL PLAN INDIACTES VIA NOTES ON A.01 THAT
 THE ELECTRICAL PANEL CERTAIN LIGHTING AND SMOKE
 DETECTORS WILL REMAIN FOR THE DURATION OF THE
 CONSTRUCTION PROCESS. INDICATE THE LOCATION OF THE
 ELECTRICAL PANEL, ELECTRICAL SERVICE, LIGHTING AND
 SMOKE DETECTORS THAT ARE EXISTING TO REMAIN.
  
 2) PROVIDE A PANEL SCHEDULE FOR CIRCUITS THAT WILL
 REMAIN. NEC 408.4
  
 3) INDICATE THE LOCATION OF THE REQUIRED GFI
 RECEPTACLES FOR CONSTRUCTION. NEC 590.6
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  