Plan Review Notes For Permit 15051133 |
Permit Number |
15051133 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-06-09 20:58:21 | ELECTRICAL PROVISO: | | UNLESS ALL SERVICE RACEWAY AND CONDUCTORS ARE ON THE | | EXTERIOR OF THE BLDG. COMPLIANCE WITH NEC 300.5(B) & AN | | EXTERNAL DISCONNECT AS IN NEC230.70 SHALL BE REQUIRED. | | |
|