Plan Review Notes For Permit 15051119 |
Permit Number |
15051119 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-06-26 07:56:20 | APPROVED WITH EXCEPTION. THIS PLAN HAS BEEN APPROVED | | PROVISIONALLY. FAILURE TO CORRECT THE LISTED | | DEFICIENCIES IN THIS PLAN PRIOR TO INSPECTION WILL | | RESULT IN FAILED INSPECTION(S) AND ASSESSMENT OF | | RE-INSPECTION FEE(S). | | 1) AN ELECTRICAL PERMIT IS REQUIRED. FBC 105.1 | | 2) THE NEW POOL EQUIPMENT AND DECK IS REQUIRED TO BE | | BONDED IN ACCORDANCE WITH 2008 NEC 680.26. | | |
|