2015-06-25 16:42:23RESIDENTIAL (R3) RE-ROOF, SECOND BUILDING REVIEW
 COMMENTS.
 CODE: 2010 FBC-RESIDENTIAL.
  
 1- ORIGINAL COMMENT:
 "FBC 109, PROVIDE A COPY OF THE CONTRACT FOR THIS JOB."
 OK. SUBMITTED. TOTAL VALUE $26,500. VALUATION AND FEES
 WILL BE ADJUSTED ACCORDINGLY
  
 2 - ORIGINAL COMMENT:
 "ON THE FOAM ADHESIVE PRODUCT APPROVAL, INDICATE METHOD
 OF INSTALLATION PROPOSED (TABLE 1), FBC 2010
 RESIDENTIAL 301".
 OK.
  
 3. ORIGINAL COMMENT:
 "THE TILE PRODUCT APPROVAL IS NOT THE MOST CURRENT
 VERSION; PLEASE PROVIDE FL 7473-R5 AND ASSOCIATED
 INSTALLATION INSTRUCTIONS/EVALUATION REPORT".
 (OK. FLORIDA WEBSITE INFORMATION IS FL7473-R3)
  
 4- NEW COMMENT TO VERIFY COMPLIANCE WITH THE DESIGN
 PRESSURES OF SEC. R301 OF 2010- FBC-RESIDENTIAL:
 TU PLUS UNDERLAYMENT SUBMITTED: NEED TO IDENTIFY
 UNDERLAYMENT WITH DESIGN PRESSURES THAT MEET THE DESIGN
 PRESSURES FOR ALL ROOF ZONES, INCLUDING THE CORNER
 AREAS. NOTE: THIS HOUSE IS LOCATED IN EXPOSURE "C". THE
 REQUIRED DESIGN PRESSURES FOR CORNER AREAS IS -95.12
 PSF.
  