Plan Review Notes
Plan Review Notes For Permit 15051084
Permit Number 15051084
Review Stop M
Sequence Number 1
Notes
Date Text
2015-06-23 13:25:02PLAN DENIED
 1) PLEASE EXPLAIN WHAT AHU- 1 IS COOLING HALLWAY OR
 CLEAN ROOM
 2) PROVIDE A ENGINEER DETAIL ON CONDENSER STAND TIED TO
 ROOF
 AND CONDENSER TIED TO STAND. PROVIDE TYPE AND SIZE
 ANCHOR USED.
 PER SECTION 301.12 WIND RESISTANCE FBC (M) 2010
 3) PROVIDE HEATING AND COOLING CALCULATIONS. PER
 SECTION
 503.2.1 FLORIDA ENERGY CODE 2010.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  