Notes |
Date |
Text |
2015-06-22 06:16:34 | 1) THE RELIEF VENT SHOWN IS UNACCEPTABLE AS DRAWN. IT | | DOES NOT MEET THE INTENT OF THE PLUMBING CODE. WHERE | | AND WHAT DOES IT CONNECT TO? COMPLY W/2010 FPC | | SEC.917.3.2. | | 2) SUBMIT THE CALCULATIONS THAT YOU USED TO SIZE THE | | GREASE TRAP UNDER THE 3 COMPARTMENT SINK. I ASKED FOR | | THIS ON MY LAST REVIEW. 2ND REQUEST. | | 3) IN MY LAST REVIEW I STATED THAT THE STACK FOR THE | | MOP SINK WAS A THREE INCH STACK. THE STACK IS A | | CONTINUOUS 3 INCH STACK, NOT A 3 INCH STACK WITH A 2 | | INCH VENT. | | 4) SUBMIT A WATER RISER FOR THE NEW MOP SINK. WPB | | AMEND. TO 2010 FBC SEC. 107.3.5.1.3. 2ND REQUEST. | | 5INDICATE ON THE PLANS IF ANY COOKING WILL BE DONE ON | | THE PREMISES AND IF SO SHOW ALL EQUIPMENT ON THE PLANS. | | 2ND REQUEST. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | |
|