2015-06-22 06:16:341) THE RELIEF VENT SHOWN IS UNACCEPTABLE AS DRAWN. IT
 DOES NOT MEET THE INTENT OF THE PLUMBING CODE. WHERE
 AND WHAT DOES IT CONNECT TO? COMPLY W/2010 FPC
 SEC.917.3.2.
 2) SUBMIT THE CALCULATIONS THAT YOU USED TO SIZE THE
 GREASE TRAP UNDER THE 3 COMPARTMENT SINK. I ASKED FOR
 THIS ON MY LAST REVIEW. 2ND REQUEST.
 3) IN MY LAST REVIEW I STATED THAT THE STACK FOR THE
 MOP SINK WAS A THREE INCH STACK. THE STACK IS A
 CONTINUOUS 3 INCH STACK, NOT A 3 INCH STACK WITH A 2
 INCH VENT.
 4) SUBMIT A WATER RISER FOR THE NEW MOP SINK. WPB
 AMEND. TO 2010 FBC SEC. 107.3.5.1.3. 2ND REQUEST.
 5INDICATE ON THE PLANS IF ANY COOKING WILL BE DONE ON
 THE PREMISES AND IF SO SHOW ALL EQUIPMENT ON THE PLANS.
 2ND REQUEST.
  