Plan Review Notes
Plan Review Notes For Permit 15051043
Permit Number 15051043
Review Stop B
Sequence Number 1
Notes
Date Text
2015-06-04 15:49:42****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
  
 1. SEE FBC 2010 ACCESSIBILITY TABLE 208.2, 8 ACCESSIBLE
 SPACES REQUIRED, FIVE PROPOSED. PLEASE REVISE.
  
 2. ONLY ONE ACCESSIBLE SPACE IS SHOWN. IF THIS IS A
 MULTI LEVEL BUILDING, AND PARKING IS ON MULTIPLE
 LEVELS, PLEASE SHOW HEIGHT AND VAN ACCESSIBLE SPACES,
 IF VAN ACCESSIBLE SPACES ARE POSSIBLE, SECTION 208.2.4.
  
 3. FBC 2010 ACCESSIBILITY 208.2.1, THE FOLLOWING USES
 HAVE ADDITIONAL PARKING REQUIREMENTS:
  
 HOSPITAL OUTPATIENT FACILITES
 REHABILITATION FACILITIES
 OUTPATIENT PHYSICAL THERAPY FACILITIES
  
 PLAN IS TO EITHER SHOW LOCATION OF TENANTS WITH ANY OF
 THE ABOVE USES OR PLAN IS TO INCLUDE A STATEMENT WHICH
 STATES THAT NONE OF THE ABOVE USES (HOSPITAL OUTPATIENT
 FACILITIES, REHABILITATION FACILITIES, OUTPATIENT
 PHYSICAL THERAPY FACILITIES) ARE AT THIS LOCATION.
  
 4. PLEASE NOTE THAT DOT DETAILS WERE USED ON THE PLAN.
 DETECTABLE WARNINGS ARE REQUIRED AT STREET CROSSINGS,
 BUT ARE NO LONGER REQUIRED AT VEHICULAR CROSSINGS WHICH
 ARE NOT STREETS. THIS WAS REMOVED FROM THE ADA (AND
 THEREFORE THE FBC) DUE TO THE PREFERENCE OF DISABLED
 PERSONS WHO HAD A CONSENSUS THAT THEY WERE POTENTIALLY
 HAZARDOUS AND WERE ALSO CONFUSING AS THEY OCCURRED TOO
 FREQUENTLY.
  
 DESIGNER MAY ELECT TO LEAVE THE DETECTABLE WARNINGS AS
 THERE IS NOTHING IN THE CODE TO PROHIBIT THEM.
  
  
  