2015-05-29 11:15:30 | PERMIT # 15050966 |
| REVIEW COMMENTS - FIRE DEPARTMENT |
| |
| WHERE MUSIC SYSTEMS ARE BEING INSTALLED IN TENANT |
| SPACES: THE SPEAKER SYSTEM WILL NEED TO BE TESTED |
| AGAINST THE FIRE ALARM SYSTEM TO ENSURE THAT THE |
| MINIMUM REQUIRED DECIBEL LEVELS OF THE FIRE ALARM |
| SYSTEM ARE BEING MET. PENDING RESULTS OF FIELD |
| INSPECTION/FIRE ALARM TEST, ADDITIONAL REQUIREMENTS MAY |
| BE NEEDED. |
| |
| PROVISO: ALL TENANT SPACES FOR THE MARKETPLACE MUST BE |
| TIED INTO THE MASTER FIRE ALARM PANEL FOR THE BUILDING. |
| EACH TENANT SPACE WILL BE INTERCONNECTED AND UPON |
| ACTIVATION OF AN ALARM IN ANY ONE SPACE, ALL SPACES |
| WILL HAVE THEIR NOTIFICATION DEVICES ACTIVATE. AN FACP |
| IN A TENANT SPACES WILL HAVE THE "RESET" AND "SILENCE" |
| FUNCTIONS DEACTIVATED. RESET AND SILENCE OF AN ALARM IS |
| LIMITED TO THE MASTER PANEL FOR THE BUILDING AND MAY |
| ONLY BE DONE BY A LICENSED FIRE ALARM TECHNICIAN. |
| SHOULD IT BE FOUND THAT TENANTS ARE ACCESSING THE |
| PANELS IN THE TENANT SPACES AND/OR USING THE "RESET" OR |
| "SILENCE" FUNCTIONS, THE OFFICE OF THE FIRE MARSHAL MAY |
| REQUIRE THAT THE TENANT FACP BE REMOVED. |
| PER APPROVED MASTER PLANS: MAIN FACP FOR THIS BUILDING |
| IS TO BE THE ONLY PANEL TO NOTIFY THE FIRE DEPARMENT. |
| NOTIFICATION WILL DESIGNATE SPECIFIC ADDRESS OF TENANT |
| WHERE TROUBLE IS LOCATED. EACH BUILDING SHALL |
| ALARM/EVACUATE ONLY THE SPACES IN THAT BUILDING (IE AN |
| ALARM IN "B" WILL NOT EVACUATE ANY SPACE IN "A", "BII", |
| OR "C". EACH TENANT SPACE FACP SHALL BE CONNECTED TO |
| MAIN FACP FOR THIS BUILDING VIA MODULES. TENANT SYSTEM |
| SHALL BE COMPATIBLE WITH NOTIFIER OR EQUAL APPROVED |
| MAIN FACP/HARDWARE EACH FLOW/TAMPER SHALL BE ZONED SO |
| THAT AN ALARM WILL SOUND FOR EACH BUILDING SEPARATELY. |
| |