Plan Review Notes
Plan Review Notes For Permit 15050879
Permit Number 15050879
Review Stop E
Sequence Number 3
Notes
Date Text
2015-10-22 19:39:18THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE 2008 EDITION
 OF THE NEC, (NATIONAL ELECTRICAL CODE); THE FBC,
 (FLORIDA BUILDING CODE) 2010, AS APPLICABLE AND BELOW
 ARE THE DEFICIENCIES NOTED.
 1. GENERAL NOTES REFERENCE TO THE 2010 NEC SHALL BE
 CORRECTED AS IT NEVER EXISTED. THE APPLICABLE CODE FOR
 THIS PROJECT IS THE 2008 EDITION.
 2. THE SHEET INDEX MAKES REFERENCE TO SHEET E1.0 FOR
 THE ELECTRIC WHICH IS NOT PROVIDED, YET SUBMITTED SHEET
 E2.1 IS NOT MENTIONED. CORRECT ACCORDINGLY.
 3. PER NEC 210.70)(A) EXCEPTION AUTOMATIC LIGHTING
 CONTROL IS REQUIRED FOR THE EXTERIOR STAIRWAYS.
 4. THE WORD ?ROMEX? AS USED IN NOTE 26.3 IS TO IDENTIFY
 A TYPE OF CABLE. ROMEX IS A BRAND NAME AND NOT A TYPE
 OF CABLE; REFER TO CABLE TYPES ?NM?, ?NMC? OR ?NMS?.
 5. NOTE 26.4 DICTATES KITCHEN COUNTER SPACING AT 36?
 CENTER CONTRARY TO NEC 210.52(C) REQUIREMENTS. CORRECT
 NOTE ACCORDINGLY.
 6. SMOKE DETECTOR IS REQUIRED INSIDE THE GARAGE
 APARTMENT.
 7. ARC-FAULT PROTECTION IS ERRONEOUSLY ONLY ADDRESSED
 FOR SMOKE DETECTOR CIRCUITS ON THE PLANS. ARC-FAULT
 PROTECTION REQUIREMENTS APPEAR IN NEC 210.12.
 8. ALL DWELLING RECEPTACLES SHALL BE LISTED
 TAMPER-RESISTANT ?TR? PER NEC 406.11.
 9. ALL OUTLETS IN WET LOCATIONS SHALL BE LISTED
 WEATHER-RESISTANT ?WR? AS INDICATED IN NEC 406.8.
 10. ALL CEILING OUTLET BOXES SHALL BE LISTED TO SUPPORT
 50#?S AS PER NEC 314.27.
 11. DWELLING UNIT RECEPTACLES SHALL BE SPACED AS
 INSTRUCTED IN NEC 210.52. AS SUCH YOU ARE MISSING
 OUTLETS IN THE FAMILY ROOM, BEHIND THE FIREPLACE,
 LIVING ROOM, BEDROOMS I & II.
 12. PORCH LIGHT SHALL BE CONTROLLED VIA A 3 WAY SWITCH
 BY ENTRY WAY.
 13. BEDROOM CORRIDOR SHALL BE PROPERLY ILLUMINATED AND
 SWITCHED PREFERABLY WITH A 3 OR 4 WAY SWITCHES.
 14. IF THE OUTLET INSIDE THE CLOSET IN BEDROOM II IS TO
 BE INTENDED FOR THE CONNECTION OF ANY EQUIPMENT, NEC
 210.70 REQUIRES THAT THERE BE A LIGHT CONTROLLED BY A
 WALL SWITCH FOR THAT ROOM.
 15. KITCHEN COUNTER OR PENINSULA OUTLETS SHALL BE AS
 DICTATED IN NEC 210.52 (C); THE PENINSULA SHALL HAVE AN
 OUTLET AS REQUIRED.
 16. THERE SHALL BE A GFI ?WR? OUTLET IN FRONT OF THE
 DWELLING PER NEC 210.52(E)(1).
 17. YOU SHALL SHOW THE REQUIRED LAUNDRY CIRCUIT 19 ON
 THE FLOOR PLAN.
 18. YOU SHALL PROVIDE ACCURATE AND SITE SPECIFIC FEEDER
 DIAGRAM AND LOAD CALCS SHOW PROPER CONDUCTOR AND GROUND
 CONDUCTOR SIZING FOR THE COMPLETE SERVICE AS MANDATED
 BY NEC 215.5.
 19. THE CONNECTED LOAD AS INDICATED EXCEEDS THE RATING
 OF THE MAIN CIRCUIT BREAKER AND BUS BAR OF PANEL P1.
 THE PLANS SHALL BE REVISED TO ADDRESS THE HEREIN
 MENTIONED ITEMS; ONCE CORRECTED SHALL BE RESUBMITTED
 FOR ANOTHER REVIEW. WHEN RESUBMITTING, YOU ARE REQUIRED
 TO PROVIDE A RESPONSE LETTER ADDRESSING EACH ITEM ALONG
 WITH THE STANDARD CITY RE-SUBMITTAL FORM. PLEASE,
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE SUBMITTAL
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARISON. CLOUDING THE CHANGES WILL BE GREATLY
 APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
  
  