2015-10-22 19:39:18 | THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION |
| HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE 2008 EDITION |
| OF THE NEC, (NATIONAL ELECTRICAL CODE); THE FBC, |
| (FLORIDA BUILDING CODE) 2010, AS APPLICABLE AND BELOW |
| ARE THE DEFICIENCIES NOTED. |
| 1. GENERAL NOTES REFERENCE TO THE 2010 NEC SHALL BE |
| CORRECTED AS IT NEVER EXISTED. THE APPLICABLE CODE FOR |
| THIS PROJECT IS THE 2008 EDITION. |
| 2. THE SHEET INDEX MAKES REFERENCE TO SHEET E1.0 FOR |
| THE ELECTRIC WHICH IS NOT PROVIDED, YET SUBMITTED SHEET |
| E2.1 IS NOT MENTIONED. CORRECT ACCORDINGLY. |
| 3. PER NEC 210.70)(A) EXCEPTION AUTOMATIC LIGHTING |
| CONTROL IS REQUIRED FOR THE EXTERIOR STAIRWAYS. |
| 4. THE WORD ?ROMEX? AS USED IN NOTE 26.3 IS TO IDENTIFY |
| A TYPE OF CABLE. ROMEX IS A BRAND NAME AND NOT A TYPE |
| OF CABLE; REFER TO CABLE TYPES ?NM?, ?NMC? OR ?NMS?. |
| 5. NOTE 26.4 DICTATES KITCHEN COUNTER SPACING AT 36? |
| CENTER CONTRARY TO NEC 210.52(C) REQUIREMENTS. CORRECT |
| NOTE ACCORDINGLY. |
| 6. SMOKE DETECTOR IS REQUIRED INSIDE THE GARAGE |
| APARTMENT. |
| 7. ARC-FAULT PROTECTION IS ERRONEOUSLY ONLY ADDRESSED |
| FOR SMOKE DETECTOR CIRCUITS ON THE PLANS. ARC-FAULT |
| PROTECTION REQUIREMENTS APPEAR IN NEC 210.12. |
| 8. ALL DWELLING RECEPTACLES SHALL BE LISTED |
| TAMPER-RESISTANT ?TR? PER NEC 406.11. |
| 9. ALL OUTLETS IN WET LOCATIONS SHALL BE LISTED |
| WEATHER-RESISTANT ?WR? AS INDICATED IN NEC 406.8. |
| 10. ALL CEILING OUTLET BOXES SHALL BE LISTED TO SUPPORT |
| 50#?S AS PER NEC 314.27. |
| 11. DWELLING UNIT RECEPTACLES SHALL BE SPACED AS |
| INSTRUCTED IN NEC 210.52. AS SUCH YOU ARE MISSING |
| OUTLETS IN THE FAMILY ROOM, BEHIND THE FIREPLACE, |
| LIVING ROOM, BEDROOMS I & II. |
| 12. PORCH LIGHT SHALL BE CONTROLLED VIA A 3 WAY SWITCH |
| BY ENTRY WAY. |
| 13. BEDROOM CORRIDOR SHALL BE PROPERLY ILLUMINATED AND |
| SWITCHED PREFERABLY WITH A 3 OR 4 WAY SWITCHES. |
| 14. IF THE OUTLET INSIDE THE CLOSET IN BEDROOM II IS TO |
| BE INTENDED FOR THE CONNECTION OF ANY EQUIPMENT, NEC |
| 210.70 REQUIRES THAT THERE BE A LIGHT CONTROLLED BY A |
| WALL SWITCH FOR THAT ROOM. |
| 15. KITCHEN COUNTER OR PENINSULA OUTLETS SHALL BE AS |
| DICTATED IN NEC 210.52 (C); THE PENINSULA SHALL HAVE AN |
| OUTLET AS REQUIRED. |
| 16. THERE SHALL BE A GFI ?WR? OUTLET IN FRONT OF THE |
| DWELLING PER NEC 210.52(E)(1). |
| 17. YOU SHALL SHOW THE REQUIRED LAUNDRY CIRCUIT 19 ON |
| THE FLOOR PLAN. |
| 18. YOU SHALL PROVIDE ACCURATE AND SITE SPECIFIC FEEDER |
| DIAGRAM AND LOAD CALCS SHOW PROPER CONDUCTOR AND GROUND |
| CONDUCTOR SIZING FOR THE COMPLETE SERVICE AS MANDATED |
| BY NEC 215.5. |
| 19. THE CONNECTED LOAD AS INDICATED EXCEEDS THE RATING |
| OF THE MAIN CIRCUIT BREAKER AND BUS BAR OF PANEL P1. |
| THE PLANS SHALL BE REVISED TO ADDRESS THE HEREIN |
| MENTIONED ITEMS; ONCE CORRECTED SHALL BE RESUBMITTED |
| FOR ANOTHER REVIEW. WHEN RESUBMITTING, YOU ARE REQUIRED |
| TO PROVIDE A RESPONSE LETTER ADDRESSING EACH ITEM ALONG |
| WITH THE STANDARD CITY RE-SUBMITTAL FORM. PLEASE, |
| ADDITIONALLY, INSERT CORRECTED PAGES INTO THE SUBMITTAL |
| AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| COMPARISON. CLOUDING THE CHANGES WILL BE GREATLY |
| APPRECIATED. |
| |
| IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| CONTACT ME DIRECTLY. |
| |
| THANK YOU, |
| MIKE ALBARRAN |
| ELECTRICAL PLANS EXAMINER |
| |
| |