Plan Review Notes For Permit 15050879 |
Permit Number |
15050879 |
|
Review Stop |
B |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2015-10-17 17:43:43 | 3RD REVIEW: FBC 2010 | | | | FBC 107, MINIMUM PLAN REVIEW CRITERIA. THIS REVIEW IS | | DENIED FOR LACK OF INFORMATION AS FOLLOWS: | | | | THE DESIGNER MUST PROVIDE FURTHER DETAILS, TO SPECIFY | | MATERIALS, CONNECTION AND ATTACHMENTS AS FOLLOWS: | | WALL SECTION SHEET A-1.2 & NOTES 09.1 & 09.2: | | ATTACHMENT OF FLOOR JOIST, CEILING JOIST, SPECFY WALL | | STUD SIZE AND OC SPACING AND ALL SHEATHING NAILING. | | | | ADDITIONAL SUBMITTAL IS NEEDED TO CLARIFY THE SELECTED | | WINDOW/DOOR, STORM PANEL AND ROOFING PRODUCTS TO BE | | USED . CLARIFY THE CONFLICT OF NOTE 08.8 VERSUS THE | | PROVIDED SLIDING GLASS DOOR NOA TO ACHIEVE IMPACT | | PROTECTION. THE OTHER DOOR SUBMITTALS ARE NOT CLEAR. A | | ROOFING PRODUCT IS NOT SUBMITTED. A COVER SHEET ONLY | | HAS BEEN PROVIDED FOR STORM PANELS. IF PANELS ARE TO BE | | USED, PROVIDE FULL INFORMATION. | | | | YOU MAY CHOOSE TO DEFER THE PRODUCT APPROVAL | | SUBMITTALS. | | | | STEVEN KENNEDY, CBO | | CHIEF PLANS EXAMINER | | (561) 805-6710 | | [email protected] | | |
|