2015-07-14 12:51:047/14/2015
 PROJECT: 347 PLYMOTH
 PERMIT#: 15050879
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC,
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER ONE,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 2ND ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW
 COMMENTS:
  
 1) THE SERVICE RISER PROVIDE IS NOT COMPLIANT.
 DISCONNECTS SHALL BE GROUPED. NEC 230.72. YOU INDICATE
 PANEL P1 TO BE LOCATED INSIDE MAIN HOUSE NEW LAUNDRY
 ROOM AND P2 TO BE LOCATED IN THE DETACHED GARAGE
 BUILDING.
  
 2) INDICATE THE LOCATION OF THE ELECTRICAL SERVICE
 METER.
  
 3) INDICATE THE SIZE AND CONTENTS OF THE EXISTING
 SERVICE RACEWAY BETWEEN THE METER AND PANEL P1. YOUR
 NOTES 26.1 ON PAGE E-2.1 INDICATE THAT YOU PROPOSE A
 NEW ELECTRICAL SERVICE WITH MAIN DISCONNECT THIS
 CONFLICTS WITH YOUR RISER DIAGRAM.
 CLARIFIFICATION REQUIRED. YOU INDICATE THE METER AND
 SERVICE ENTRANCE CONDUCTORS TO PANEL P1 ARE EXISTING
 AND YET PANEL P1 IS A NEW PANEL AND ACCORDING TO PAGE
 A-1.0 IT IS IN A NEW LOCATION.
 YOU ALSO INDICATE PANEL P2 IS FED THROUGH P1 HOWEVER
 THERE IS NO INDICATION OF AN OCPD IN PANEL P1 TO FEED
 P2. IN ADDITION THE NOTES ON PAGE E-2.1 INDICATE A NEW
 UNDERGROUND TO THE EXISTING SERVICE. THERFORE THE
 SERVICE RISER AND SITE/FLOOR PLAN NEED CLARIFICATION.
  
 4) INDICATE ALL REQUIRED SMOKE DETECTORS. YOU HAVE
 INDICATED SMOKE DETECTORS OUTSIDE OF THE SLEEPING ROOMS
 BUT NOT INSIDE. ALSO GIVE CAREFUL CONSIDERATION TO THE
 REQUIREMENTS IN THE FBC-R 315 CARBON MONOXIDE
 DETECTORS. WHEN ALTERATIONS, REPAIRS, OR ADDITIONS
 REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING
 ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE
 INDIVIDUAL DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE
 ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS.
 FBC-RESIDENTIAL 314 AND 315.
  
 5) PROVIDE CLARIFICATION AT THE ELECTRICAL PANEL. EVERY
 CIRCUIT AND CIRCUIT MODIFICATION SHALL BE LEGIBLY
 IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND SPECIFIC
 PURPOSE OR USE. NEC 408.4 SPECIFICALLY THE WATER HEATER
 IN BOTH PANELS. THE SYSTEM VOLTAGE AND LOAD SHOULD BE
 CLEAR. YOU HAVE INDICATED THE WIRE SIZE AND IN MOST
 CASES THE NUMBER OF POLES USED BUT THE OCPD SIZE HAS
 NOT BEEN INDICATED. PLEASE CLARIFY.
  
 6) PROVIDE DISCONNECTS AT AHU'S NEC 440.14
  
 7) INDICATE GFI AS GEQUIRED IN THE KITCHEN FOR
 COUNTERTOP OUTLETS. NEC 210.8(6)
  
 8) VERIFY CLEARANCES REQUIRED FOR ELECTRICAL PANEL AND
 ELECTRICAL EQUIPMENT REQUIRING SERVICE. NEC 110.26
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  