2015-07-14 12:51:04 | 7/14/2015 |
| PROJECT: 347 PLYMOTH |
| PERMIT#: 15050879 |
| CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC, |
| 2010 WPB AMENDMENTS TO THE FBC, CHAPTER ONE, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| 2ND ELECTRICAL PLAN REVIEW |
| ACTION: DENIED |
| |
| REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW |
| COMMENTS: |
| |
| 1) THE SERVICE RISER PROVIDE IS NOT COMPLIANT. |
| DISCONNECTS SHALL BE GROUPED. NEC 230.72. YOU INDICATE |
| PANEL P1 TO BE LOCATED INSIDE MAIN HOUSE NEW LAUNDRY |
| ROOM AND P2 TO BE LOCATED IN THE DETACHED GARAGE |
| BUILDING. |
| |
| 2) INDICATE THE LOCATION OF THE ELECTRICAL SERVICE |
| METER. |
| |
| 3) INDICATE THE SIZE AND CONTENTS OF THE EXISTING |
| SERVICE RACEWAY BETWEEN THE METER AND PANEL P1. YOUR |
| NOTES 26.1 ON PAGE E-2.1 INDICATE THAT YOU PROPOSE A |
| NEW ELECTRICAL SERVICE WITH MAIN DISCONNECT THIS |
| CONFLICTS WITH YOUR RISER DIAGRAM. |
| CLARIFIFICATION REQUIRED. YOU INDICATE THE METER AND |
| SERVICE ENTRANCE CONDUCTORS TO PANEL P1 ARE EXISTING |
| AND YET PANEL P1 IS A NEW PANEL AND ACCORDING TO PAGE |
| A-1.0 IT IS IN A NEW LOCATION. |
| YOU ALSO INDICATE PANEL P2 IS FED THROUGH P1 HOWEVER |
| THERE IS NO INDICATION OF AN OCPD IN PANEL P1 TO FEED |
| P2. IN ADDITION THE NOTES ON PAGE E-2.1 INDICATE A NEW |
| UNDERGROUND TO THE EXISTING SERVICE. THERFORE THE |
| SERVICE RISER AND SITE/FLOOR PLAN NEED CLARIFICATION. |
| |
| 4) INDICATE ALL REQUIRED SMOKE DETECTORS. YOU HAVE |
| INDICATED SMOKE DETECTORS OUTSIDE OF THE SLEEPING ROOMS |
| BUT NOT INSIDE. ALSO GIVE CAREFUL CONSIDERATION TO THE |
| REQUIREMENTS IN THE FBC-R 315 CARBON MONOXIDE |
| DETECTORS. WHEN ALTERATIONS, REPAIRS, OR ADDITIONS |
| REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING |
| ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE |
| INDIVIDUAL DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE |
| ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS. |
| FBC-RESIDENTIAL 314 AND 315. |
| |
| 5) PROVIDE CLARIFICATION AT THE ELECTRICAL PANEL. EVERY |
| CIRCUIT AND CIRCUIT MODIFICATION SHALL BE LEGIBLY |
| IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND SPECIFIC |
| PURPOSE OR USE. NEC 408.4 SPECIFICALLY THE WATER HEATER |
| IN BOTH PANELS. THE SYSTEM VOLTAGE AND LOAD SHOULD BE |
| CLEAR. YOU HAVE INDICATED THE WIRE SIZE AND IN MOST |
| CASES THE NUMBER OF POLES USED BUT THE OCPD SIZE HAS |
| NOT BEEN INDICATED. PLEASE CLARIFY. |
| |
| 6) PROVIDE DISCONNECTS AT AHU'S NEC 440.14 |
| |
| 7) INDICATE GFI AS GEQUIRED IN THE KITCHEN FOR |
| COUNTERTOP OUTLETS. NEC 210.8(6) |
| |
| 8) VERIFY CLEARANCES REQUIRED FOR ELECTRICAL PANEL AND |
| ELECTRICAL EQUIPMENT REQUIRING SERVICE. NEC 110.26 |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. SEE LINK: |
| HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| |
| A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| THIS REVIEW. |
| ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| REVIEW. |
| DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| 561-805-6717 OR [email protected] |
| |
2015-07-11 13:26:23 | 2ND REVIEW: FBC 2010 |
| |
| UNDER REVIEW - SENT TO DAVID HAYES |
| |
| |