2015-07-11 13:26:07 | 2ND REVIEW: FBC 2010 |
| |
| NEW COMMENTS: |
| |
| PROVIDE DETAILS FOR EACH SET OF THE NEW STAIRS, |
| LANDINGS, AND HANDRAILS. |
| |
| EXPLAIN TO WHICH PART OF THE BUILDING THE WALL SECTION |
| ON SHEET A-1.2 APPLIES. |
| |
| FBC 107.3.5.1.6 ENERGY CALCULATIONS - PROVIDE AN ENERGY |
| SUBMITTAL. |
| |
| THE PROJECT QUALIFIES AS A RENOVATION AS THE PROPOSED |
| COST EXCEEDS 30% OF THE VALUE OF THE EXISTING |
| STRICTURE. |
| |
| FBCE-103.2.1.1 RESIDENTIAL LESS THAN OR EQUAL TO 3 |
| STORIES. |
| |
| FBCE-103.2.1.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE. |
| AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM 402 |
| SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO |
| DEMONSTRATE CODE COMPLIANCE BY THIS METHOD. |
| |
| FBCE-103.2.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE. |
| AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM 405 |
| (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE |
| SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE |
| COMPLIANCE BY SECTION 405. |
| |
| PREVIOUS COMMENTS: |
| |
| PROVIDE STRUCTURAL DETAILS FOR ALTERATIONS OF OPENINGS |
| TO ACCOMODATE THE INSTALLATION OF NEW WINDOW AND DOOR |
| PRODUCTS, AS MAY BE NECESSARY. |
| |
| ADDITIONALLY, THE PLAN NOTES ARE IN CONFLICT WITH THE |
| PRODUCT APPROVALS AND NOTE 08.1 & 08.2 ON SHEET A-1.1 |
| INDICATING IMPACT RESISTANT WINDOWS, SPECIFYING NON |
| IMPACT, AND ALSO PROVIDING STORM PANELS. PLEASE FURTHER |
| EVALUATE THESE ISSUES AND SPECFY WHAT IS SPECIFICALLY |
| PROPOSED. |
| |
| THE DESIGN PRESSURES PROVIDED SHOULD BE SPECIFIC TO |
| EACH OPENING. YOU HAVE APPARENTLY PROVIDED A ONLY |
| GENERAL ZONE INFORMATION. |
| |
| |
| |
| |
| |
| |