Plan Review Notes For Permit 15050879 |
Permit Number |
15050879 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-06-04 06:43:17 | 1ST REVIEW: FBC 2010 | | | | FBC 107 PLEASE PROVIDE ADDITIONAL DETAILS AS FOLLOWS: | | | | STRUCTURAL DETAIL FOR ALTERATIONS OF OPENINGS TO | | ACCOMODATE THE INSTALLATION OF NEW WINDOW AND DOOR | | PRODUCTS, AS MAY BE NECESSARY. | | | | THE ARCHITECTS LETTER OF 4/17/15 INDICATES FL 15227-68M | | WILL BE USED AS AN EXTERIOR SWING DOOR. THE PROVIDED | | DOOR PRODUCT INFORMATION IS BY A MANUFACTURER | | INCONSISTENT WITH THE ONE FOUND UNDER THIS NUMBER AT | | HTTPS://FLORIDABUILDING.ORG/PR/PR_DEFAULT.ASPX | | | | THE ARCHITECTS LETTER OF 4/17/15 INDICATES FL 13578-R1 | | WILL BE USED FOR STEEL SHUTTERS. THE PRODUCT | | INFORMATION IS NOT PROVIDED. | | | | NOTE: IT MAY BE ADVISABLE FOR THE DESIGNER OR A | | CONSULTANT ENGINEER TO REVIEW THE WINDOW AND DOOR | | PRODUCTS FURTHER AND PROVIDE ADDITION ANALYSIS AS TO | | DESIGN PRESSURES AND TO PROVIDE AN INSTALLATION | | SCHEDULE FOR THE SHUTTERS. | | YOU MAY WISH TO UTILIZE THE SCHEDULE FOUND AT: HTTP://W | | PB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/2013/09/ | | SCHEDULE_FOR_INSTALLATION.PDF | | | | PLEASE INDICATE THE METHOD INTENDED FOR COMPLIANCE WITH | | FBC-R311.1 AS TO EGRESS WHEN THE BUILDING IS SHUTTERED. | | | | STEVEN KENNEDY, CBO | | CHIEF PLANS EXAMINER | | (561) 805-6710 | | [email protected] | | |
|