2015-06-02 11:08:32 | 2ND REVIEW: FBC 2010 |
| |
| SUBMIT AN ADEQUATE PLAN AS PREVIOUSLY NOTED. PERHAPS |
| YOU SHOULD CONSIDER HAVING AN ENGINEERED DESIGN. YOUR |
| DESIGN INDICATES A 12" WIDE FOOTING WITH AN 8" BLOCK |
| WALL AND ONLY #5 IN THE FOOTING. YOU INDICATE THE WALL |
| WILL RETAIN SOMETHING, BUT YOU DO NOT IDENTIFY WHAT IS |
| WILL RETAIN. WHAT IS THE RELATIONSHIP OF THE FOOTING |
| DEPTH TO THE FINALA GRADE, AND THE HEIGHT OF WALL TO |
| FINAL GRADE? IS DIRT BEING RETAINED? WILL A 12" WIDE |
| FOOTING RESIST THE MOMENT IMPOSED ON IT BY RETAINED |
| DIRT ON POSSIBLY ONLY ONE SIDE? |
| |
| FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN |
| UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE |
| OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE |
| AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT |
| IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| DETERMINED BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND |
| SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM |
| OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS, |
| WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE |
| TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC, |
| AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE |
| OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS |
| EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS |
| AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE |
| OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO |
| SECTION 107.3.5). |
| |
| |