2015-07-04 05:31:34 | 1) THE GREASE INTERCEPTOR SIZING CALCULATIONS FROM |
| SCHIER SHOW THAT THREE GB-250 GREASE INTERCEPTORS ARE |
| REQUIRED FOR THIS PROJECT BUT ONLY ONE IS CALLED OUT ON |
| THE PLANS. THE PLANS SHALL SHOW ALL THREE INTERCEPTORS |
| ON SHEETS P.01 & P.03. IF THE INTERCEPTORS WILL BE |
| LOCATED IN A TRAFFIC AREA THEY SHALL BE PROTECTED WITH |
| TRAFFIC LIDS.SHOW THE LOCATION OF THE INTERCEPTORS ALSO |
| ON SHT. A.01. WPB AMEND. TO 2010 FBC 107.2.1. THE |
| INSTALLATION SHALL COMPLY WITH THE SPECIFICATION FROM |
| THE CITY WPB ENGINEERING DEPT. DRAWING # GS-7.1. |
| 2) THE PREVIOUS PLAN SHOWED THE WASTE FROM KITCHEN |
| EQUIPMENT #1 ( BLAST MACHINE) GOING TO THE SANITARY AND |
| NOW IT IS GOING TO A DRYWELL. SUBMIT MANUF. |
| SPECIFICATIONS FOR THE PIECE OF EQUIPMENT AND INDICATE |
| ON THE PLAN THE SPECIFIC TYPE OF WASTE THAT WILL BE |
| DISCHARGE FROM THIS MACHINE. IF IT IS ANYTHING OTHER |
| THAN UNCONTAMINATED CLEAR WATER WASTE IT SHALL NOT |
| DISCHARGE TO THE DRYWELL. IF IT REQUIRES PRE-TREATMENT |
| IT WILL HAVE TO DISCHARGE TO THE GREASE INTERCEPTOR. IF |
| NOT, IT SHALL DISCHARGE TO THE SANITARY. MY PREVIOUS |
| COMMENT REFERRED TO THE CONDENSATE FROM THE WALK-IN |
| FREEZERS DISCHARGING TO THE SANITARY. |
| 3) SHT. P.03 - THE GAS PIPING DIAGRAM SHOWS THE |
| TANKLESS WATER HEATER AS A RINNAI AND THE WATER PIPING |
| DIAGRAM SHOWS A NORITZ AND THE SUBMITTED SPECS ARE FOR |
| A NORITZ. WHICH IS IT? SUBMIT THE CORRECT SPECS FOR THE |
| UNIT BEING INSTALLED. |
| 4) SHT. P.03 - THE VENT THAT WAS INCREASED TO 3 INCH |
| SHALL BE INCREASED FOR THE ENTIRE DEVELOPED LENGTH AS |
| STATED IN THE 2010 FPC SEC. 916.2. THE SANITARY RISER |
| SHOWS A 2" VENT INCREASING TO 3". THIS DOES NOT MEET |
| THE INTENT OF THE CODE. |
| |
| |
| |
| |
| |
| |
| |
| PLUMBING PLAN REVIEW - |
| TIM LARGE |
| CHIEF PLUMBING INSPECTOR |