Plan Review Notes For Permit 15050842 |
Permit Number |
15050842 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2015-07-06 14:45:34 | THE REVISED SET OF DRAWINGS NOW HAS A ROOF PLANS WHICH | | IS LACKING THE GFCI SERVICE OUTLETS REQUIRED BY NEC | | 210.63 | | I TRIED TO FOLLOW YOUR THE NEW PLANS TO LOCATE THE | | NOTES IN RESPONSE TO COMMENTS 1, 3 & 5, AND WAS UNABLE | | TO FIND THEM. THESE NOTES NEED TO BE ADDED TO THE | | DRAWINGS AND CLOUDED. | | MY NOTE #8 REFERS TO SPECIFIC IDENTIFICATION OR MARKING | | REQUIREMENTS AS WELL AS SECURITY OR MECHANICAL | | PROTECTION REQUIREMENTS OF THE NFPA 72, SECTION | | 10.6.5.2. | | | | PLEASE CORRECT THE PLANS ACCORDINGLY AND RESUBMIT. IF | | YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO | | CONTACT ME. | | MIKE ALBARRAN 561-805-6746 |
|