Plan Review Notes
Plan Review Notes For Permit 15050842
Permit Number 15050842
Review Stop P
Sequence Number 1
Notes
Date Text
2015-06-06 08:20:441) SUBMIT MANUFACTURER SPECIFICATIONS FOR THE EQUIPMET
 TO BE USED IN THE MANUFACTURING PROCESS.2010 FPC
 SEC.303.2, WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 2) A MINIMUM OF 2 DRINKING FOUNTAINS SHALL BE PROVIDED
 IN ACCORDANCE WITH 2010 FL. ACCESS. CODE SEC.211.2.
 3) SUBMIT MANUF. SPEC SHEETS FOR THE WATER HEATER. WPB
 AMEND. TO 2010 FBC SEC. 107.2.1.
 4) SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR THE WATER
 HEATER PER 2010 FGC SEC. 304.1.
 5) ALL HOSE BIBBS SHALL BE SEPARATELY VALVED PER FPC
 SEC.606.2.
 6) SHT. A.03 - THE EQUIPMENT SCHEDULE NOTES ITEM #15 AS
 A GENERATOR BUT I DO NOT SEE THIS ON THE PLANS.
 CLARIFY.
 7) INDICATE THE PSI OF THE GAS SYSTEM.THE SIZING CANNOT
 BE CHECKED WITHOUT THE PSI INFORMATION.
 8) SUBMIT SIZING CALCULATIONS FOR THE GREASE
 INTERCEPTORS. THE CALCULATIONS SHALL BE REVIEWED AND
 APPROVED BY SCIER IN ACCORDANCE WITH 2010 FPC
 SEC.1003.2. CONTACT LEE SCHNEEWEISS AT 1-800-538-4792.
 9) THE BRANCHVENTING APPEARS TO BE OVER 40 FEET IN
 DEVELOPED LENGTH. THE VENT SHALL BE INCREASED ONE PIPE
 SIZE TO A MINIMUM OF 3 " PER 2010 FPC SEC.916.2 &
 916.4.1.
 10) THE PLANS SHOW CONDENSATE LINES DISCHARGING INTO
 THE SANITARY SYSTEM. CLEAR WATER WASTE SHALL NOT
 DISCHARGE TO THE SANITARY SYSTEM PER WPB CITY ORDINANCE
 SEC. 90-126 ( B) (5).
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  